Minuteman UPS, ENERGY STAR certified
Minuteman EC2000RTXL2U
2,000 VA / 1,800 W double conversion UPS, model number 90000782.
Capacity
2,000 VA
1,800 W real power
Topology
Double Conversion
Efficiency
91.7%
weighted, as tested
Runtime @ 50%
10 min
3 min at full load
A UPS has two ratings and the lower one is the limit. This unit is rated 2,000 VA and 1,800 W, so the equipment plugged into its battery outlets should draw no more than about 1,440 W if you want the usual 20% headroom. How to size a UPS.
Its weighted efficiency of 91.7% compares with a median of 98.3% across 183 certified units within 25% of its capacity. With nothing plugged in it still draws 30.8 W, about $35 a year at 13¢/kWh just to stand ready.
- Maker
- Minuteman
- Model
- EC2000RTXL2U
- Model number
- 90000782
- Apparent power rating
- 2,000 VA
- Real power rating
- 1,800 W
- Power factor
- 0.90
- Topology
- Double Conversion
- Intended use
- Commercial
- Battery
- Valve Regulated Lead-acid Battery
- Runtime at 50% load
- 10 min
- Runtime at 100% load
- 3 min
- Battery warranty
- 3 yr
- Weighted efficiency
- 91.7%
- Efficiency at 25 / 50 / 75 / 100% load
- 87.7% / 91.2% / 92.0% / 91.9%
- Input power at no load
- 30.8 W
- Outlets
- 6 (6 battery + surge, 0 surge only)
- Rack mountable
- Yes, 2U
- Modular
- Yes
- Rated input voltage
- 120 V
- Rated output voltage
- 120 V
- Connections
- Serial Port,Other,Ethernet,USB Port
- Size (H x W x D)
- 88 x 479 x 487 mm
- Maker take-back program
- Yes
- On the market since
- Jan 2025
- ENERGY STAR certified
- 18 Dec 2024
Source: ENERGY STAR certified uninterruptible power supplies dataset, US EPA, record 3892655, data build 2026-09-29. Figures are as the maker certified them. How we use this data.
Other makers
Machines comparable to the EC2000RTXL2U
Certified UPS units from other makers within 25% of its VA rating.
| Model | Capacity | Topology | Efficiency | Runtime @ 50% |
|---|---|---|---|---|
| CyberPower PR2000RTXL2U | 2,000 VA / 2,000 W | Line Interactive | 98.0% | 13 min |
| Delta RT-2K | 2,000 VA / 1,800 W | Double Conversion | 92.2% | 12 min |
| Liebert GXT5-2000LVRT2UXL | 2,000 VA / 1,800 W | Multi-Mode Double Conversion | 92.5% | 9 min |
| Vertiv GXT5-2000LVRT2UXL | 2,000 VA / 1,800 W | Multi-Mode Double Conversion | 92.5% | 9 min |
| Eaton 9PX2000RT | 2,000 VA / 1,800 W | Double Conversion | 92.5% | 20 min |
| CyberPower OR2200PFCRT2U | 2,000 VA / 1,540 W | Line Interactive | 98.2% | 13 min |
Minuteman
More Minuteman UPS battery backups
| Model | Capacity | Topology | Efficiency | Runtime @ 50% |
|---|---|---|---|---|
| EC1000RTXL2U | 1,000 VA / 900 W | Double Conversion | 90.9% | 10 min |
| EC1500RTXL2U | 1,500 VA / 1,350 W | Double Conversion | 91.1% | 10 min |
| EC3000RTXL2U | 3,000 VA / 2,700 W | Double Conversion | 91.9% | 10 min |
| ED10KRT | 10 kVA / 9,000 W | Double Conversion | 93.9% | 7 min |
| ED5KRT | 5,000 VA / 4,500 W | Double Conversion | 93.8% | 11 min |
| ED6KRT | 6,000 VA / 5,400 W | Double Conversion | 93.9% | 7 min |
| ED8KRT | 8,000 VA / 7,200 W | Double Conversion | 94.1% | 11 min |
| EN450G | 450 VA / 250 W | Passive Standby | 97.9% | 10 min |