Vertiv UPS, ENERGY STAR certified

Vertiv GXT5-2000LVRT2UXL

2,000 VA / 1,800 W multi-mode double conversion UPS.

Capacity

2,000 VA

1,800 W real power

Topology

Multi-Mode Double Conversion

Efficiency

92.5%

weighted, as tested

Runtime @ 50%

9 min

3 min at full load

A UPS has two ratings and the lower one is the limit. This unit is rated 2,000 VA and 1,800 W, so the equipment plugged into its battery outlets should draw no more than about 1,440 W if you want the usual 20% headroom. How to size a UPS.

Its weighted efficiency of 92.5% compares with a median of 98.3% across 183 certified units within 25% of its capacity. With nothing plugged in it still draws 27.8 W, about $32 a year at 13¢/kWh just to stand ready.

Maker
Vertiv
Model
GXT5-2000LVRT2UXL
Apparent power rating
2,000 VA
Real power rating
1,800 W
Power factor
0.90
Topology
Multi-Mode Double Conversion
Intended use
Consumer, Commercial, Data Center
Battery
Valve Regulated Lead-acid Battery
Runtime at 50% load
9 min
Runtime at 100% load
3 min
Battery warranty
2 yr
Weighted efficiency
92.5%
Efficiency at 25 / 50 / 75 / 100% load
90.9% / 92.7% / 92.4% / 92.3%
Input power at no load
27.8 W
Rack mountable
Yes
Rated input voltage
110-125 V
Rated output voltage
110-125 V
Connections
USB Port,Ethernet
Size (H x W x D)
85 x 430 x 470 mm
Maker take-back program
No
On the market since
Dec 2018
ENERGY STAR certified
6 Dec 2018

Certified under the same record

The maker lists these as the same machine or a variant of it: GXT5-2000LVRT2UXLB, GXT5-2000LVRT3UXLB.

Source: ENERGY STAR certified uninterruptible power supplies dataset, US EPA, record 2331008, data build 2026-09-29. Figures are as the maker certified them. How we use this data.

Other makers

Machines comparable to the GXT5-2000LVRT2UXL

Certified UPS units from other makers within 25% of its VA rating.

ModelCapacityTopologyEfficiencyRuntime @ 50%
CyberPower PR2000RTXL2U2,000 VA / 2,000 WLine Interactive98.0%13 min
Delta RT-2K2,000 VA / 1,800 WDouble Conversion92.2%12 min
Liebert GXT5-2000LVRT2UXL2,000 VA / 1,800 WMulti-Mode Double Conversion92.5%9 min
Eaton 9PX2000RT2,000 VA / 1,800 WDouble Conversion92.5%20 min
CyberPower OR2200PFCRT2U2,000 VA / 1,540 WLine Interactive98.2%13 min
CyberPower OR2200LCDRT2U2,000 VA / 1,320 WLine Interactive98.8%13 min

Vertiv

More Vertiv UPS battery backups

ModelCapacityTopologyEfficiencyRuntime @ 50%
10B14763GG103450 kVA / 405 kWMulti-Mode Double Conversion97.2%30 min
10B14789GF103825 kVA / 743 kWMulti-Mode Double Conversion97.7%30 min
47SA040A[0|1|2|3][C|Y][0|F|H|M|G|L][0|1]10 kVA / 10 kWMulti-Mode Double Conversion94.2%34 min
47SA100A[0|1|2|3][C|Y][0|F|H|M|G|L][0|1]60 kVA / 60 kWMulti-Mode Double Conversion95.8%10 min
47SA120A[0|1|2|3][C|Y][0|F|H|M|G|L][0|1]120 kVA / 120 kWMulti-Mode Double Conversion95.6%10 min
51SA030QAA30 kVA / 30 kWMulti-Mode Double Conversion96.3%10 min
51SA030QBA30 kVA / 30 kWMulti-Mode Double Conversion95.2%10 min
51SA050BAA50 kVA / 50 kWMulti-Mode Double Conversion96.4%10 min

All Vertiv UPS battery backups