Middle Atlantic UPX-OL2000R-2

2,000 VA / 1,800 W other UPS.

Capacity

2,000 VA

1,800 W real power

Topology

Other

Efficiency

91.3%

weighted, as tested

Runtime @ 50%

9 min

2 min at full load

A UPS has two ratings and the lower one is the limit. This unit is rated 2,000 VA and 1,800 W, so the equipment plugged into its battery outlets should draw no more than about 1,440 W if you want the usual 20% headroom. How to size a UPS.

Its weighted efficiency of 91.3% compares with a median of 98.3% across 183 certified units within 25% of its capacity. With nothing plugged in it still draws 26.4 W, about $30 a year at 13¢/kWh just to stand ready.

Maker
Middle Atlantic
Model
UPX-OL2000R-2
Apparent power rating
2,000 VA
Real power rating
1,800 W
Power factor
0.90
Topology
Other
Intended use
Commercial
Battery
Valve Regulated Lead-acid Battery
Runtime at 50% load
9 min
Runtime at 100% load
2 min
Battery warranty
3 yr
Weighted efficiency
91.3%
Efficiency at 25 / 50 / 75 / 100% load
90.5% / 91.9% / 91.4% / 90.4%
Input power at no load
26.4 W
Rack mountable
No
Rated input voltage
110-127 V
Rated output voltage
110-127 V
Connections
Serial Port,USB Port
Size (H x W x D)
87 x 440 x 440 mm
Maker take-back program
Yes
On the market since
Mar 2024
ENERGY STAR certified
21 Nov 2023

Certified under the same record

The maker lists these as the same machine or a variant of it: UPX-OL2000R-8, UPX-RLNK-OL2000R-2, UPX-RLNK-OL2000R-8.

Source: ENERGY STAR certified uninterruptible power supplies dataset, US EPA, record 2765581, data build 2026-09-29. Figures are as the maker certified them. How we use this data.

Other makers

Machines comparable to the UPX-OL2000R-2

Certified UPS units from other makers within 25% of its VA rating.

ModelCapacityTopologyEfficiencyRuntime @ 50%
CyberPower PR2000RTXL2U2,000 VA / 2,000 WLine Interactive98.0%13 min
Delta RT-2K2,000 VA / 1,800 WDouble Conversion92.2%12 min
Liebert GXT5-2000LVRT2UXL2,000 VA / 1,800 WMulti-Mode Double Conversion92.5%9 min
Vertiv GXT5-2000LVRT2UXL2,000 VA / 1,800 WMulti-Mode Double Conversion92.5%9 min
Eaton 9PX2000RT2,000 VA / 1,800 WDouble Conversion92.5%20 min
CyberPower OR2200PFCRT2U2,000 VA / 1,540 WLine Interactive98.2%13 min

Middle Atlantic

More Middle Atlantic UPS battery backups

ModelCapacityTopologyEfficiencyRuntime @ 50%
UPX-2000R-82,000 VA / 1,800 WLine Interactive98.5%10 min
UPX-OL1000R-21,000 VA / 1,000 WOther91.0%9 min
UPX-OL1500R-21,500 VA / 1,350 WOther91.1%9 min
UPX-OL3000R-23,000 VA / 2,700 WOther92.1%11 min

All Middle Atlantic UPS battery backups