Middle Atlantic UPS, ENERGY STAR certified
Middle Atlantic UPX-OL3000R-2
3,000 VA / 2,700 W other UPS.
Capacity
3,000 VA
2,700 W real power
Topology
Other
Efficiency
92.1%
weighted, as tested
Runtime @ 50%
11 min
3 min at full load
A UPS has two ratings and the lower one is the limit. This unit is rated 3,000 VA and 2,700 W, so the equipment plugged into its battery outlets should draw no more than about 2,160 W if you want the usual 20% headroom. How to size a UPS.
Its weighted efficiency of 92.1% compares with a median of 93.1% across 95 certified units within 25% of its capacity. With nothing plugged in it still draws 50.8 W, about $58 a year at 13¢/kWh just to stand ready.
- Maker
- Middle Atlantic
- Model
- UPX-OL3000R-2
- Apparent power rating
- 3,000 VA
- Real power rating
- 2,700 W
- Power factor
- 0.90
- Topology
- Other
- Intended use
- Commercial
- Battery
- Other
- Runtime at 50% load
- 11 min
- Runtime at 100% load
- 3 min
- Battery warranty
- 3 yr
- Weighted efficiency
- 92.1%
- Efficiency at 25 / 50 / 75 / 100% load
- 89.7% / 92.2% / 92.3% / 91.7%
- Input power at no load
- 50.8 W
- Rack mountable
- No
- Rated input voltage
- 110-127 V
- Rated output voltage
- 110-127 V
- Connections
- Serial Port,USB Port
- Size (H x W x D)
- 87 x 452 x 599 mm
- Maker take-back program
- Yes
- On the market since
- Dec 2024
- ENERGY STAR certified
- 3 Dec 2024
Certified under the same record
The maker lists these as the same machine or a variant of it: UPX-OL3000R-6, UPX-RLNK-OL3000R-2, UPX-RLNK-OL3000R-6.
Source: ENERGY STAR certified uninterruptible power supplies dataset, US EPA, record 3845110, data build 2026-09-29. Figures are as the maker certified them. How we use this data.
Other makers
Machines comparable to the UPX-OL3000R-2
Certified UPS units from other makers within 25% of its VA rating.
| Model | Capacity | Topology | Efficiency | Runtime @ 50% |
|---|---|---|---|---|
| CyberPower PR3000RTXL2UHVA | 3,000 VA / 3,000 W | Line Interactive | 98.9% | 11 min |
| Delta RT-3K | 3,000 VA / 2,700 W | Double Conversion | 92.0% | 12 min |
| CyberPower OL3000RTXL2UHV | 3,000 VA / 2,700 W | Double Conversion | 92.0% | 11 min |
| CyberPower OL3000RTXL2UHVN | 3,000 VA / 2,700 W | Double Conversion | 92.0% | 11 min |
| CyberPower OL3000RTXL2UHVTAA | 3,000 VA / 2,700 W | Double Conversion | 92.0% | 11 min |
| CyberPower OL3000RT JP | 3,000 VA / 2,700 W | Double Conversion | 91.5% | 11 min |
Middle Atlantic
More Middle Atlantic UPS battery backups
| Model | Capacity | Topology | Efficiency | Runtime @ 50% |
|---|---|---|---|---|
| UPX-2000R-8 | 2,000 VA / 1,800 W | Line Interactive | 98.5% | 10 min |
| UPX-OL1000R-2 | 1,000 VA / 1,000 W | Other | 91.0% | 9 min |
| UPX-OL1500R-2 | 1,500 VA / 1,350 W | Other | 91.1% | 9 min |
| UPX-OL2000R-2 | 2,000 VA / 1,800 W | Other | 91.3% | 9 min |