Liebert eXM 0080kTK16FN01000

80 kVA / 80 kW multi-mode double conversion UPS.

Capacity

80 kVA

80 kW real power

Topology

Multi-Mode Double Conversion

Efficiency

95.8%

weighted, as tested

Runtime @ 50%

10 min

5 min at full load

A UPS has two ratings and the lower one is the limit. This unit is rated 80 kVA and 80 kW, so the equipment plugged into its battery outlets should draw no more than about 64 kW if you want the usual 20% headroom. How to size a UPS.

Its weighted efficiency of 95.8% compares with a median of 96.2% across 29 certified units within 25% of its capacity. With nothing plugged in it still draws 512.7 W, about $584 a year at 13¢/kWh just to stand ready.

Maker
Liebert
Model
eXM 0080kTK16FN01000
Apparent power rating
80 kVA
Real power rating
80 kW
Power factor
1.00
Topology
Multi-Mode Double Conversion
Intended use
Consumer, Commercial, Data Center
Battery
Valve Regulated Lead-acid Battery
Runtime at 50% load
10 min
Runtime at 100% load
5 min
Battery warranty
3 yr
Weighted efficiency
95.8%
Efficiency at 25 / 50 / 75 / 100% load
95.5% / 96.2% / 95.8% / 95.5%
Input power at no load
512.7 W
Rack mountable
No
Rated input voltage
228-478 V
Rated output voltage
380-415 V
Connections
Serial Port,Other,USB Port,Ethernet
Size (H x W x D)
2000 x 600 x 1000 mm
Maker take-back program
No
On the market since
Nov 2015
ENERGY STAR certified
23 Jan 2019

Source: ENERGY STAR certified uninterruptible power supplies dataset, US EPA, record 2336439, data build 2026-09-29. Figures are as the maker certified them. How we use this data.

Other makers

Machines comparable to the eXM 0080kTK16FN01000

Certified UPS units from other makers within 25% of its VA rating.

ModelCapacityTopologyEfficiencyRuntime @ 50%
Vertiv eXM 0080kTK16FN0100080 kVA / 80 kWMulti-Mode Double Conversion95.8%10 min
Schneider Electric Galaxy VS UPS 100kW 480V80 kVA / 80 kWMulti-Mode Double Conversion96.2%5 min
Schneider Electric GVSUPS100K0B5GS80 kVA / 80 kWMulti-Mode Double Conversion96.2%-
Schneider Electric GVSUPS80K0B5GS80 kVA / 80 kWMulti-Mode Double Conversion96.2%-
Schneider Electric Galaxy VS UPS 80kW 480V80 kVA / 80 kWMulti-Mode Double Conversion96.2%7 min
Eaton S3M80K80 kVA / 80 kWDouble Conversion95.8%-

Liebert

More Liebert UPS battery backups

ModelCapacityTopologyEfficiencyRuntime @ 50%
10B14763GG103450 kVA / 405 kWMulti-Mode Double Conversion97.2%30 min
10B14789GF103825 kVA / 743 kWMulti-Mode Double Conversion97.7%30 min
47SA040A[0|1|2|3][C|Y][0|F|H|M|G|L][0|1]10 kVA / 10 kWMulti-Mode Double Conversion94.2%34 min
47SA100A[0|1|2|3][C|Y][0|F|H|M|G|L][0|1]60 kVA / 60 kWMulti-Mode Double Conversion95.8%10 min
47SA120A[0|1|2|3][C|Y][0|F|H|M|G|L][0|1]120 kVA / 120 kWMulti-Mode Double Conversion95.6%10 min
51SA030QAA30 kVA / 30 kWMulti-Mode Double Conversion96.3%10 min
51SA030QBA30 kVA / 30 kWMulti-Mode Double Conversion95.2%10 min
51SA050BAA50 kVA / 50 kWMulti-Mode Double Conversion96.4%10 min

All Liebert UPS battery backups