Schneider Electric GVSUPS80K0B5GS
80 kVA / 80 kW multi-mode double conversion UPS.
Galaxy VS UPS 80kW 480V for up to 5 internal 9Ah smart modular battery strings, Start-up 5x8
Capacity
80 kVA
80 kW real power
Topology
Multi-Mode Double Conversion
Efficiency
96.2%
weighted, as tested
Runtime @ 50%
-
not reported by the maker
A UPS has two ratings and the lower one is the limit. This unit is rated 80 kVA and 80 kW, so the equipment plugged into its battery outlets should draw no more than about 64 kW if you want the usual 20% headroom. How to size a UPS.
Its weighted efficiency of 96.2% compares with a median of 96.2% across 29 certified units within 25% of its capacity. With nothing plugged in it still draws 478.1 W, about $544 a year at 13¢/kWh just to stand ready.
- Maker
- Schneider Electric
- Model
- GVSUPS80K0B5GS
- Description
- Galaxy VS UPS 80kW 480V for up to 5 internal 9Ah smart modular battery strings, Start-up 5x8
- Apparent power rating
- 80 kVA
- Real power rating
- 80 kW
- Power factor
- 1.00
- Topology
- Multi-Mode Double Conversion
- Intended use
- Data Center
- Battery
- Valve Regulated Lead-acid Battery
- Weighted efficiency
- 96.2%
- Efficiency at 25 / 50 / 75 / 100% load
- 95.3% / 96.4% / 96.7% / 96.7%
- Input power at no load
- 478.1 W
- Rack mountable
- No
- Rated input voltage
- 480 V
- Rated output voltage
- 480 V
- Connections
- Serial Port,Ethernet
- Size (H x W x D)
- 1970 x 550 x 847 mm
- Maker take-back program
- Yes
- On the market since
- Feb 2020
- ENERGY STAR certified
- 12 Mar 2020
Source: ENERGY STAR certified uninterruptible power supplies dataset, US EPA, record 2356236, data build 2026-09-29. Figures are as the maker certified them. How we use this data.
Other makers
Machines comparable to the GVSUPS80K0B5GS
Certified UPS units from other makers within 25% of its VA rating.
| Model | Capacity | Topology | Efficiency | Runtime @ 50% |
|---|---|---|---|---|
| Liebert eXM 0080kTK16FN01000 | 80 kVA / 80 kW | Multi-Mode Double Conversion | 95.8% | 10 min |
| Vertiv eXM 0080kTK16FN01000 | 80 kVA / 80 kW | Multi-Mode Double Conversion | 95.8% | 10 min |
| Eaton S3M80K | 80 kVA / 80 kW | Double Conversion | 95.8% | - |
| Vertiv Liebert EXS Fr3 series | 60 kVA / 60 kW | Multi-Mode Double Conversion | 95.4% | 20 min |
| Liebert EXS Fr3 series | 60 kVA / 60 kW | Multi-Mode Double Conversion | 95.4% | 20 min |
| Liebert 47SA100A[0|1|2|3][C|Y][0|F|H|M|G|L][0|1] | 60 kVA / 60 kW | Multi-Mode Double Conversion | 95.8% | 10 min |
Schneider Electric
More Schneider Electric UPS battery backups
| Model | Capacity | Topology | Efficiency | Runtime @ 50% |
|---|---|---|---|---|
| Galaxy VL UPS 500 kW 400/480V Start-up 5x8 | 200 kVA / 200 kW | Multi-Mode Double Conversion | 96.9% | - |
| Galaxy VM 160 kVA UPS Parallel 480-480 V, 65kAIC | 160 kVA / 144 kW | Double Conversion | 96.8% | - |
| Galaxy VM 160 kVA UPS Single 480-480 V, 65kAIC, | 160 kVA / 144 kW | Double Conversion | 96.8% | - |
| Galaxy VM 180 kVA UPS Parallel 480-480 V, 65kAIC | 180 kVA / 162 kW | Double Conversion | 96.9% | - |
| Galaxy VM 180 kVA UPS Single 480-480 V, 65kAIC | 180 kVA / 162 kW | Double Conversion | 96.9% | - |
| Galaxy VM 225 kVA UPS Parallel 480-480 V, 65kAIC | 225 kVA / 202.5 kW | Double Conversion | 97.0% | - |
| Galaxy VM 225 kVA UPS Single 480-480 V, 65kAIC, | 225 kVA / 202.5 kW | Double Conversion | 97.0% | - |
| Galaxy VS 100kW 480V w/o Batteries, Start-up 5x8 | 20 kVA / 20 kW | Multi-Mode Double Conversion | 95.9% | - |