Liebert UPS, ENERGY STAR certified
Liebert 47SA040A[0|1|2|3][C|Y][0|F|H|M|G|L][0|1]
10 kVA / 10 kW multi-mode double conversion UPS.
Capacity
10 kVA
10 kW real power
Topology
Multi-Mode Double Conversion
Efficiency
94.2%
weighted, as tested
Runtime @ 50%
34 min
17 min at full load
A UPS has two ratings and the lower one is the limit. This unit is rated 10 kVA and 10 kW, so the equipment plugged into its battery outlets should draw no more than about 8,000 W if you want the usual 20% headroom. How to size a UPS.
Its weighted efficiency of 94.2% compares with a median of 95.1% across 62 certified units within 25% of its capacity. With nothing plugged in it still draws 265.5 W, about $302 a year at 13¢/kWh just to stand ready.
- Maker
- Liebert
- Model
- 47SA040A[0|1|2|3][C|Y][0|F|H|M|G|L][0|1]
- Apparent power rating
- 10 kVA
- Real power rating
- 10 kW
- Power factor
- 1.00
- Topology
- Multi-Mode Double Conversion
- Intended use
- Consumer, Commercial, Data Center
- Battery
- Flywheel
- Runtime at 50% load
- 34 min
- Runtime at 100% load
- 17 min
- Battery warranty
- 1 yr
- Weighted efficiency
- 94.2%
- Efficiency at 25 / 50 / 75 / 100% load
- 89.3% / 93.2% / 94.5% / 94.9%
- Input power at no load
- 265.5 W
- Rack mountable
- No
- Modular
- Yes
- Rated input voltage
- 176-253 V
- Rated output voltage
- 198-231 V
- Connections
- Serial Port,Other,USB Port,Ethernet
- Size (H x W x D)
- 2000 x 600 x 1000 mm
- Maker take-back program
- No
- On the market since
- Aug 2014
- ENERGY STAR certified
- 23 Jan 2019
Certified under the same record
The maker lists these as the same machine or a variant of it: Liebert eXM, 47SA010A[0|1|2|3][C|Y][0|F|H|M|G|L][0|1], 47SA015A[0|1|2|3][C|Y][0|F|H|M|G|L][0|1], 47SA020A[0|1|2|3][C|Y][0|F|H|M|G|L][0|1], 47SA030A[0|1|2|3][C|Y][0|F|H|M|G|L][0|1].
Source: ENERGY STAR certified uninterruptible power supplies dataset, US EPA, record 2335122, data build 2026-09-29. Figures are as the maker certified them. How we use this data.
Other makers
Machines comparable to the 47SA040A[0|1|2|3][C|Y][0|F|H|M|G|L][0|1]
Certified UPS units from other makers within 25% of its VA rating.
| Model | Capacity | Topology | Efficiency | Runtime @ 50% |
|---|---|---|---|---|
| Delta RT-10K | 10 kVA / 10 kW | Double Conversion | 95.2% | 12 min |
| Vertiv GXT5-10KIRT5UXLN | 10 kVA / 10 kW | Multi-Mode Double Conversion | 95.1% | 7 min |
| Vertiv GXE-10k00TLA102C00 | 10 kVA / 9,000 W | Multi-Mode Double Conversion | 95.5% | 19 min |
| Vertiv GXT5-10KMVRT6UXLN | 10 kVA / 10 kW | Multi-Mode Double Conversion | 93.9% | 9 min |
| Vertiv GXT4-10000RT230 | 10 kVA / 9,000 W | Multi-Mode Double Conversion | 93.2% | 10 min |
| Vertiv ITA-10k00ALA102P00 | 10 kVA / 10 kW | Multi-Mode Double Conversion | 95.6% | 63 min |
Liebert
More Liebert UPS battery backups
| Model | Capacity | Topology | Efficiency | Runtime @ 50% |
|---|---|---|---|---|
| 10B14763GG103 | 450 kVA / 405 kW | Multi-Mode Double Conversion | 97.2% | 30 min |
| 10B14789GF103 | 825 kVA / 743 kW | Multi-Mode Double Conversion | 97.7% | 30 min |
| 47SA100A[0|1|2|3][C|Y][0|F|H|M|G|L][0|1] | 60 kVA / 60 kW | Multi-Mode Double Conversion | 95.8% | 10 min |
| 47SA120A[0|1|2|3][C|Y][0|F|H|M|G|L][0|1] | 120 kVA / 120 kW | Multi-Mode Double Conversion | 95.6% | 10 min |
| 51SA030QAA | 30 kVA / 30 kW | Multi-Mode Double Conversion | 96.3% | 10 min |
| 51SA030QBA | 30 kVA / 30 kW | Multi-Mode Double Conversion | 95.2% | 10 min |
| 51SA050BAA | 50 kVA / 50 kW | Multi-Mode Double Conversion | 96.4% | 10 min |
| 51SA160AQA | 40 kVA / 40 kW | Multi-Mode Double Conversion | 95.5% | 10 min |