UPS battery backupsENERGY STAR certified
Eaton SU2200RTXLCD2U
2,000 VA / 1,800 W double conversion UPS.
Capacity
2,000 VA
1,800 W real power
Topology
Double Conversion
Efficiency
90.9%
weighted, as tested
Runtime @ 50%
9 min
4 min at full load
A UPS has two ratings and the lower one is the limit. This unit is rated 2,000 VA and 1,800 W, so the equipment plugged into its battery outlets should draw no more than about 1,440 W if you want the usual 20% headroom. How to size a UPS.
Its weighted efficiency of 90.9% compares with a median of 98.3% across 183 certified units within 25% of its capacity.
- Maker
- Eaton
- Model
- SU2200RTXLCD2U
- Apparent power rating
- 2,000 VA
- Real power rating
- 1,800 W
- Power factor
- 0.90
- Topology
- Double Conversion
- Intended use
- Consumer, Commercial, Data Center
- Battery
- Other
- Runtime at 50% load
- 9 min
- Runtime at 100% load
- 4 min
- Battery warranty
- 2 yr
- Weighted efficiency
- 90.9%
- Efficiency at 25 / 50 / 75 / 100% load
- - / 91.4% / 91.7% / 91.1%
- Rack mountable
- Yes, 2U
- Rated input voltage
- 100-125 V
- Rated output voltage
- 100-125 V
- Connections
- Other
- Size (H x W x D)
- 86 x 440 x 570 mm
- Maker take-back program
- No
- On the market since
- Nov 2024
- ENERGY STAR certified
- 12 Dec 2022
Certified under the same record
The maker lists these as the same machine or a variant of it: SU2200RTXLCD2UTAA, SU2200RTXLCDN.
Source: ENERGY STAR certified uninterruptible power supplies dataset, US EPA, record 2405654, data build 2026-09-29. Figures are as the maker certified them. How we use this data.
Other makers
Machines comparable to the SU2200RTXLCD2U
Certified UPS units from other makers within 25% of its VA rating.
| Model | Capacity | Topology | Efficiency | Runtime @ 50% |
|---|---|---|---|---|
| CyberPower PR2000RTXL2U | 2,000 VA / 2,000 W | Line Interactive | 98.0% | 13 min |
| Delta RT-2K | 2,000 VA / 1,800 W | Double Conversion | 92.2% | 12 min |
| Liebert GXT5-2000LVRT2UXL | 2,000 VA / 1,800 W | Multi-Mode Double Conversion | 92.5% | 9 min |
| Vertiv GXT5-2000LVRT2UXL | 2,000 VA / 1,800 W | Multi-Mode Double Conversion | 92.5% | 9 min |
| CyberPower OR2200PFCRT2U | 2,000 VA / 1,540 W | Line Interactive | 98.2% | 13 min |
| CyberPower OR2200LCDRT2U | 2,000 VA / 1,320 W | Line Interactive | 98.8% | 13 min |
Eaton
More Eaton UPS battery backups
| Model | Capacity | Topology | Efficiency | Runtime @ 50% |
|---|---|---|---|---|
| 5P1000RT2UG2-L | 1,000 VA / 920 W | Line Interactive | 98.6% | 18 min |
| 5P1150IRT2UG2-L | 1,150 VA / 920 W | Line Interactive | 98.5% | 18 min |
| 5P1550IRT2UG2-L | 1,550 VA / 1,350 W | Line Interactive | 98.9% | 12 min |
| 5P1550RT2UG2-L | 1,440 VA / 1,350 W | Line Interactive | 98.7% | 12 min |
| 5P550RG2-L | 550 VA / 495 W | Line Interactive | 98.5% | 18 min |
| 5P650IRG2-L | 650 VA / 520 W | Line Interactive | 98.4% | 16 min |
| 5PX1000IRT2UG2 | 1,000 VA / 1,000 W | Line Interactive | 98.5% | 17 min |
| 5PX1000RTG2 | 1,000 VA / 1,000 W | Line Interactive | 98.5% | 16 min |