Skip to content

UPS battery backupsENERGY STAR certified

Delta DPH-250K-HV

250 kVA / 250 kW multi-mode double conversion UPS.

Capacity

250 kVA

250 kW real power

Topology

Multi-Mode Double Conversion

Efficiency

94.9%

weighted, as tested

Runtime @ 50%

10 min

3 min at full load

A UPS has two ratings and the lower one is the limit. This unit is rated 250 kVA and 250 kW, so the equipment plugged into its battery outlets should draw no more than about 200 kW if you want the usual 20% headroom. How to size a UPS.

Its weighted efficiency of 94.9% compares with a median of 96.9% across 17 certified units within 25% of its capacity. With nothing plugged in it still draws 545.2 W, about $621 a year at 13¢/kWh just to stand ready.

Maker
Delta
Model
DPH-250K-HV
Apparent power rating
250 kVA
Real power rating
250 kW
Power factor
1.00
Topology
Multi-Mode Double Conversion
Intended use
Data Center
Battery
Valve Regulated Lead-acid Battery
Runtime at 50% load
10 min
Runtime at 100% load
3 min
Battery warranty
3 yr
Weighted efficiency
94.9%
Efficiency at 25 / 50 / 75 / 100% load
94.7% / 95.2% / 95.5% / 95.5%
Input power at no load
545.2 W
Rack mountable
No
Modular
Yes
Rated input voltage
480 V
Rated output voltage
480 V
Connections
Serial Port,Other,Ethernet,USB Port
Size (H x W x D)
2000 x 600 x 850 mm
Maker take-back program
No
On the market since
Mar 2024
ENERGY STAR certified
9 Jan 2024

Source: ENERGY STAR certified uninterruptible power supplies dataset, US EPA, record 3360624, data build 2026-09-29. Figures are as the maker certified them. How we use this data.

Other makers

Machines comparable to the DPH-250K-HV

Certified UPS units from other makers within 25% of its VA rating.

ModelCapacityTopologyEfficiencyRuntime @ 50%
Liebert 51SA250NAA250 kVA / 250 kWMulti-Mode Double Conversion96.6%10 min
Vertiv 51SA250NAA250 kVA / 250 kWMulti-Mode Double Conversion96.6%10 min
Vertiv PowerUPS 9000 1250kVA250 kVA / 250 kWMulti-Mode Double Conversion97.7%60 min
Vertiv PowerUPS 9000 1250kVA250 kVA / 250 kWMulti-Mode Double Conversion97.2%60 min
Schneider Electric Galaxy VM 225 kVA UPS Parallel 480-480 V, 65kAIC225 kVA / 202.5 kWDouble Conversion97.0%-
Schneider Electric GVMRB225KG65S225 kVA / 202.5 kWDouble Conversion97.0%-

Delta

More Delta UPS battery backups

ModelCapacityTopologyEfficiencyRuntime @ 50%
DPH-105K-LV15 kVA / 15 kWMulti-Mode Double Conversion95.6%-
DPH-150K-HV50 kVA / 50 kWMulti-Mode Double Conversion96.3%23 min
DPH-300K-HV50 kVA / 50 kWMulti-Mode Double Conversion96.3%12 min
DPH-500K-HV200 kVA / 200 kWMulti-Mode Double Conversion99.1%11 min
DPH-60K-LV15 kVA / 15 kWMulti-Mode Double Conversion95.5%12 min
RT PRO-1K1,000 VA / 1,000 WMulti-Mode Double Conversion91.4%10 min
RT PRO-2K2,000 VA / 2,000 WMulti-Mode Double Conversion93.4%12 min
RT PRO-3K3,000 VA / 3,000 WMulti-Mode Double Conversion93.6%14 min

All Delta UPS battery backups