Vertiv UPS, ENERGY STAR certified
Vertiv PowerUPS 9000 1250kVA
250 kVA / 250 kW multi-mode double conversion UPS, model number 9000 0250kMK16FN0200.
Capacity
250 kVA
250 kW real power
Topology
Multi-Mode Double Conversion
Efficiency
97.2%
weighted, as tested
Runtime @ 50%
60 min
30 min at full load
A UPS has two ratings and the lower one is the limit. This unit is rated 250 kVA and 250 kW, so the equipment plugged into its battery outlets should draw no more than about 200 kW if you want the usual 20% headroom. How to size a UPS.
Its weighted efficiency of 97.2% compares with a median of 96.9% across 17 certified units within 25% of its capacity. With nothing plugged in it still draws 957.0 W, about $1,090 a year at 13¢/kWh just to stand ready.
- Maker
- Vertiv
- Model
- PowerUPS 9000 1250kVA
- Model number
- 9000 0250kMK16FN0200
- Apparent power rating
- 250 kVA
- Real power rating
- 250 kW
- Power factor
- 1.00
- Topology
- Multi-Mode Double Conversion
- Intended use
- Consumer, Commercial, Data Center
- Battery
- Vented Lead-acid Battery
- Runtime at 50% load
- 60 min
- Runtime at 100% load
- 30 min
- Battery warranty
- 1 yr
- Weighted efficiency
- 97.2%
- Efficiency at 25 / 50 / 75 / 100% load
- 97.2% / 97.4% / 96.9% / 96.4%
- Input power at no load
- 957.0 W
- Rack mountable
- No
- Modular
- Yes
- Rated input voltage
- 415 V
- Rated output voltage
- 415 V
- Connections
- Serial Port,Ethernet
- Size (H x W x D)
- 2000 x 2700 x 1000 mm
- Maker take-back program
- No
- On the market since
- Sep 2025
- ENERGY STAR certified
- 31 Jul 2025
Certified under the same record
The maker lists these as the same machine or a variant of it: 9000 0375kMK16FN0200, 9000 0500kMK16FN0200, 9000 0600kMK16FN0200, 9000 0625kMK16FN0200, 9000 0750kMK16FN0200, 9000 0800kMK16FN0200, 9000 0875kMK16FN0200, 9000 1000kMK16FN0200, 9000 1100kMK16FN0200, 9000 1125kMK16FN0200, 9000 1200kMK16FN0200, 9000 1250kMK16FN0200, PowerUPS 9000, P90100(d)A(f)(g)(h)CB(k)(l)(m)(n)(o)(p), P90110(d)A(f)(g)(h)CB(k)(l)(m)(n)(o)(p), P90120(d)A(f)(g)(h)CB(k)(l)(m)(n)(o)(p), P901A0(d)A(f)(g)(h)CB(k)(l)(m)(n)(o)(p), P901B0(d)A(f)(g)(h)CB(k)(l)(m)(n)(o)(p), (d)=1, 2, 3, 4 (f)=C, D (g)=A, B (h)=N.
Source: ENERGY STAR certified uninterruptible power supplies dataset, US EPA, record 4480893, data build 2026-09-29. Figures are as the maker certified them. How we use this data.
Other makers
Machines comparable to the PowerUPS 9000 1250kVA
Certified UPS units from other makers within 25% of its VA rating.
| Model | Capacity | Topology | Efficiency | Runtime @ 50% |
|---|---|---|---|---|
| Liebert 51SA250NAA | 250 kVA / 250 kW | Multi-Mode Double Conversion | 96.6% | 10 min |
| Delta DPH-250K-HV | 250 kVA / 250 kW | Multi-Mode Double Conversion | 94.9% | 10 min |
| Schneider Electric Galaxy VM 225 kVA UPS Parallel 480-480 V, 65kAIC | 225 kVA / 202.5 kW | Double Conversion | 97.0% | - |
| Schneider Electric GVMRB225KG65S | 225 kVA / 202.5 kW | Double Conversion | 97.0% | - |
| Schneider Electric Galaxy VM 225 kVA UPS Single 480-480 V, 65kAIC, | 225 kVA / 202.5 kW | Double Conversion | 97.0% | - |
| Mitsubishi 9900Aegis Series | 225 kVA / 202.5 kW | Double Conversion | 96.5% | - |
Vertiv
More Vertiv UPS battery backups
| Model | Capacity | Topology | Efficiency | Runtime @ 50% |
|---|---|---|---|---|
| 10B14763GG103 | 450 kVA / 405 kW | Multi-Mode Double Conversion | 97.2% | 30 min |
| 10B14789GF103 | 825 kVA / 743 kW | Multi-Mode Double Conversion | 97.7% | 30 min |
| 47SA040A[0|1|2|3][C|Y][0|F|H|M|G|L][0|1] | 10 kVA / 10 kW | Multi-Mode Double Conversion | 94.2% | 34 min |
| 47SA100A[0|1|2|3][C|Y][0|F|H|M|G|L][0|1] | 60 kVA / 60 kW | Multi-Mode Double Conversion | 95.8% | 10 min |
| 47SA120A[0|1|2|3][C|Y][0|F|H|M|G|L][0|1] | 120 kVA / 120 kW | Multi-Mode Double Conversion | 95.6% | 10 min |
| 51SA030QAA | 30 kVA / 30 kW | Multi-Mode Double Conversion | 96.3% | 10 min |
| 51SA030QBA | 30 kVA / 30 kW | Multi-Mode Double Conversion | 95.2% | 10 min |
| 51SA050BAA | 50 kVA / 50 kW | Multi-Mode Double Conversion | 96.4% | 10 min |