Skip to content

UPS battery backupsENERGY STAR certified

Delta DPH-60K-LV

15 kVA / 15 kW multi-mode double conversion UPS.

Capacity

15 kVA

15 kW real power

Topology

Multi-Mode Double Conversion

Efficiency

95.5%

weighted, as tested

Runtime @ 50%

12 min

3 min at full load

A UPS has two ratings and the lower one is the limit. This unit is rated 15 kVA and 15 kW, so the equipment plugged into its battery outlets should draw no more than about 12 kW if you want the usual 20% headroom. How to size a UPS.

Its weighted efficiency of 95.5% compares with a median of 94.6% across 13 certified units within 25% of its capacity. With nothing plugged in it still draws 111.8 W, about $127 a year at 13¢/kWh just to stand ready.

Maker
Delta
Model
DPH-60K-LV
Apparent power rating
15 kVA
Real power rating
15 kW
Power factor
1.00
Topology
Multi-Mode Double Conversion
Intended use
Commercial, Data Center
Battery
Valve Regulated Lead-acid Battery
Runtime at 50% load
12 min
Runtime at 100% load
3 min
Battery warranty
3 yr
Weighted efficiency
95.5%
Efficiency at 25 / 50 / 75 / 100% load
94.1% / 95.0% / 94.5% / 93.6%
Input power at no load
111.8 W
Rack mountable
No
Modular
Yes
Rated input voltage
120-127 V
Rated output voltage
120-127 V
Connections
Ethernet,USB Port
Size (H x W x D)
2000 x 600 x 850 mm
Maker take-back program
No
On the market since
Nov 2018
ENERGY STAR certified
20 Jan 2020

Certified under the same record

The maker lists these as the same machine or a variant of it: DPH-45K-LV.

Source: ENERGY STAR certified uninterruptible power supplies dataset, US EPA, record 2354254, data build 2026-09-29. Figures are as the maker certified them. How we use this data.

Other makers

Machines comparable to the DPH-60K-LV

Certified UPS units from other makers within 25% of its VA rating.

ModelCapacityTopologyEfficiencyRuntime @ 50%
Liebert GXT5-15KMVRT11UXLN15 kVA / 15 kWMulti-Mode Double Conversion94.4%9 min
Vertiv GXT5-15KMVRT11UXLN15 kVA / 15 kWMulti-Mode Double Conversion94.4%9 min
TRIPPLITE S3M15K2B15 kVA / 15 kWMulti-Mode Line Interactive94.3%25 min
Vertiv Liebert EXS F5 15k series15 kVA / 15 kWMulti-Mode Double Conversion95.0%9 min
Liebert EXS F5 15k series15 kVA / 15 kWMulti-Mode Double Conversion95.0%9 min
Liebert ITA2 15KVA15 kVA / 15 kWMulti-Mode Double Conversion94.5%23 min

Delta

More Delta UPS battery backups

ModelCapacityTopologyEfficiencyRuntime @ 50%
DPH-105K-LV15 kVA / 15 kWMulti-Mode Double Conversion95.6%-
DPH-150K-HV50 kVA / 50 kWMulti-Mode Double Conversion96.3%23 min
DPH-250K-HV250 kVA / 250 kWMulti-Mode Double Conversion94.9%10 min
DPH-300K-HV50 kVA / 50 kWMulti-Mode Double Conversion96.3%12 min
DPH-500K-HV200 kVA / 200 kWMulti-Mode Double Conversion99.1%11 min
RT PRO-1K1,000 VA / 1,000 WMulti-Mode Double Conversion91.4%10 min
RT PRO-2K2,000 VA / 2,000 WMulti-Mode Double Conversion93.4%12 min
RT PRO-3K3,000 VA / 3,000 WMulti-Mode Double Conversion93.6%14 min

All Delta UPS battery backups