UPS battery backupsENERGY STAR certified
Schneider Electric GVMRB225KG65S
225 kVA / 202.5 kW double conversion UPS.
Galaxy VM 225 kVA Additional UPS for 1+1 480-480 V
Capacity
225 kVA
202.5 kW real power
Topology
Double Conversion
Efficiency
97.0%
weighted, as tested
Runtime @ 50%
-
not reported by the maker
A UPS has two ratings and the lower one is the limit. This unit is rated 225 kVA and 202.5 kW, so the equipment plugged into its battery outlets should draw no more than about 162 kW if you want the usual 20% headroom. How to size a UPS.
Its weighted efficiency of 97.0% compares with a median of 96.9% across 21 certified units within 25% of its capacity. With nothing plugged in it still draws 1,038.0 W, about $1,182 a year at 13¢/kWh just to stand ready.
- Maker
- Schneider Electric
- Model
- GVMRB225KG65S
- Description
- Galaxy VM 225 kVA Additional UPS for 1+1 480-480 V
- Apparent power rating
- 225 kVA
- Real power rating
- 202.5 kW
- Power factor
- 0.90
- Topology
- Double Conversion
- Intended use
- Data Center
- Battery
- Valve Regulated Lead-acid Battery
- Weighted efficiency
- 97.0%
- Efficiency at 25 / 50 / 75 / 100% load
- 95.8% / 96.4% / 96.6% / 96.4%
- Input power at no load
- 1,038.0 W
- Rack mountable
- No
- Rated input voltage
- 480 V
- Rated output voltage
- 480 V
- Connections
- Serial Port,Ethernet
- Size (H x W x D)
- 1970 x 1002 x 854 mm
- Maker take-back program
- Yes
- On the market since
- Sep 2015
- ENERGY STAR certified
- 26 Feb 2019
Certified under the same record
The maker lists these as the same machine or a variant of it: GVMRB225KGS.
Source: ENERGY STAR certified uninterruptible power supplies dataset, US EPA, record 2333994, data build 2026-09-29. Figures are as the maker certified them. How we use this data.
Other makers
Machines comparable to the GVMRB225KG65S
Certified UPS units from other makers within 25% of its VA rating.
| Model | Capacity | Topology | Efficiency | Runtime @ 50% |
|---|---|---|---|---|
| Mitsubishi 9900Aegis Series | 225 kVA / 202.5 kW | Double Conversion | 96.5% | - |
| Liebert 51SA250NAA | 250 kVA / 250 kW | Multi-Mode Double Conversion | 96.6% | 10 min |
| Vertiv 51SA250NAA | 250 kVA / 250 kW | Multi-Mode Double Conversion | 96.6% | 10 min |
| Liebert 51SA200LAA | 200 kVA / 200 kW | Multi-Mode Double Conversion | 96.5% | 10 min |
| Vertiv 51SA200LAA | 200 kVA / 200 kW | Multi-Mode Double Conversion | 96.5% | 10 min |
| Liebert eXM 0200kTK16FN01000 | 200 kVA / 200 kW | Multi-Mode Double Conversion | 96.1% | 10 min |
Schneider Electric
More Schneider Electric UPS battery backups
| Model | Capacity | Topology | Efficiency | Runtime @ 50% |
|---|---|---|---|---|
| Galaxy VL UPS 500 kW 400/480V Start-up 5x8 | 200 kVA / 200 kW | Multi-Mode Double Conversion | 96.9% | - |
| Galaxy VM 160 kVA UPS Parallel 480-480 V, 65kAIC | 160 kVA / 144 kW | Double Conversion | 96.8% | - |
| Galaxy VM 160 kVA UPS Single 480-480 V, 65kAIC, | 160 kVA / 144 kW | Double Conversion | 96.8% | - |
| Galaxy VM 180 kVA UPS Parallel 480-480 V, 65kAIC | 180 kVA / 162 kW | Double Conversion | 96.9% | - |
| Galaxy VM 180 kVA UPS Single 480-480 V, 65kAIC | 180 kVA / 162 kW | Double Conversion | 96.9% | - |
| Galaxy VM 225 kVA UPS Parallel 480-480 V, 65kAIC | 225 kVA / 202.5 kW | Double Conversion | 97.0% | - |
| Galaxy VM 225 kVA UPS Single 480-480 V, 65kAIC, | 225 kVA / 202.5 kW | Double Conversion | 97.0% | - |
| Galaxy VS 100kW 480V w/o Batteries, Start-up 5x8 | 20 kVA / 20 kW | Multi-Mode Double Conversion | 95.9% | - |