Schneider Electric GVMRB225KG65S

225 kVA / 202.5 kW double conversion UPS.

Galaxy VM 225 kVA Additional UPS for 1+1 480-480 V

Capacity

225 kVA

202.5 kW real power

Topology

Double Conversion

Efficiency

97.0%

weighted, as tested

Runtime @ 50%

-

not reported by the maker

A UPS has two ratings and the lower one is the limit. This unit is rated 225 kVA and 202.5 kW, so the equipment plugged into its battery outlets should draw no more than about 162 kW if you want the usual 20% headroom. How to size a UPS.

Its weighted efficiency of 97.0% compares with a median of 96.9% across 21 certified units within 25% of its capacity. With nothing plugged in it still draws 1,038.0 W, about $1,182 a year at 13¢/kWh just to stand ready.

Maker
Schneider Electric
Model
GVMRB225KG65S
Description
Galaxy VM 225 kVA Additional UPS for 1+1 480-480 V
Apparent power rating
225 kVA
Real power rating
202.5 kW
Power factor
0.90
Topology
Double Conversion
Intended use
Data Center
Battery
Valve Regulated Lead-acid Battery
Weighted efficiency
97.0%
Efficiency at 25 / 50 / 75 / 100% load
95.8% / 96.4% / 96.6% / 96.4%
Input power at no load
1,038.0 W
Rack mountable
No
Rated input voltage
480 V
Rated output voltage
480 V
Connections
Serial Port,Ethernet
Size (H x W x D)
1970 x 1002 x 854 mm
Maker take-back program
Yes
On the market since
Sep 2015
ENERGY STAR certified
26 Feb 2019

Certified under the same record

The maker lists these as the same machine or a variant of it: GVMRB225KGS.

Source: ENERGY STAR certified uninterruptible power supplies dataset, US EPA, record 2333994, data build 2026-09-29. Figures are as the maker certified them. How we use this data.

Other makers

Machines comparable to the GVMRB225KG65S

Certified UPS units from other makers within 25% of its VA rating.

ModelCapacityTopologyEfficiencyRuntime @ 50%
Mitsubishi 9900Aegis Series225 kVA / 202.5 kWDouble Conversion96.5%-
Liebert 51SA250NAA250 kVA / 250 kWMulti-Mode Double Conversion96.6%10 min
Vertiv 51SA250NAA250 kVA / 250 kWMulti-Mode Double Conversion96.6%10 min
Liebert 51SA200LAA200 kVA / 200 kWMulti-Mode Double Conversion96.5%10 min
Vertiv 51SA200LAA200 kVA / 200 kWMulti-Mode Double Conversion96.5%10 min
Liebert eXM 0200kTK16FN01000200 kVA / 200 kWMulti-Mode Double Conversion96.1%10 min

Schneider Electric

More Schneider Electric UPS battery backups

ModelCapacityTopologyEfficiencyRuntime @ 50%
Galaxy VL UPS 500 kW 400/480V Start-up 5x8200 kVA / 200 kWMulti-Mode Double Conversion96.9%-
Galaxy VM 160 kVA UPS Parallel 480-480 V, 65kAIC160 kVA / 144 kWDouble Conversion96.8%-
Galaxy VM 160 kVA UPS Single 480-480 V, 65kAIC,160 kVA / 144 kWDouble Conversion96.8%-
Galaxy VM 180 kVA UPS Parallel 480-480 V, 65kAIC180 kVA / 162 kWDouble Conversion96.9%-
Galaxy VM 180 kVA UPS Single 480-480 V, 65kAIC180 kVA / 162 kWDouble Conversion96.9%-
Galaxy VM 225 kVA UPS Parallel 480-480 V, 65kAIC225 kVA / 202.5 kWDouble Conversion97.0%-
Galaxy VM 225 kVA UPS Single 480-480 V, 65kAIC,225 kVA / 202.5 kWDouble Conversion97.0%-
Galaxy VS 100kW 480V w/o Batteries, Start-up 5x820 kVA / 20 kWMulti-Mode Double Conversion95.9%-

All Schneider Electric UPS battery backups