UPS battery backupsENERGY STAR certified
Panduit U02N16L-N
2,000 VA / 1,800 W multi-mode double conversion UPS.
Capacity
2,000 VA
1,800 W real power
Topology
Multi-Mode Double Conversion
Efficiency
92.7%
weighted, as tested
Runtime @ 50%
120 min
60 min at full load
A UPS has two ratings and the lower one is the limit. This unit is rated 2,000 VA and 1,800 W, so the equipment plugged into its battery outlets should draw no more than about 1,440 W if you want the usual 20% headroom. How to size a UPS.
Its weighted efficiency of 92.7% compares with a median of 98.3% across 183 certified units within 25% of its capacity.
- Maker
- Panduit
- Model
- U02N16L-N
- Apparent power rating
- 2,000 VA
- Real power rating
- 1,800 W
- Power factor
- 0.90
- Topology
- Multi-Mode Double Conversion
- Intended use
- Consumer, Commercial, Data Center
- Battery
- Lithium-ion Battery
- Runtime at 50% load
- 120 min
- Runtime at 100% load
- 60 min
- Battery warranty
- 5 yr
- Weighted efficiency
- 92.7%
- Efficiency at 25 / 50 / 75 / 100% load
- 90.6% / 92.7% / 92.8% / 92.5%
- Outlets
- 8 (8 battery + surge, 0 surge only)
- Rack mountable
- Yes, 2U
- Rated input voltage
- 100-125 V
- Rated output voltage
- 100-125 V
- Connections
- Other,Ethernet,USB Port
- Size (H x W x D)
- 86 x 440 x 500 mm
- Maker take-back program
- No
- On the market since
- Jan 2026
- ENERGY STAR certified
- 22 Jan 2026
Source: ENERGY STAR certified uninterruptible power supplies dataset, US EPA, record 4528718, data build 2026-09-29. Figures are as the maker certified them. How we use this data.
Other makers
Machines comparable to the U02N16L-N
Certified UPS units from other makers within 25% of its VA rating.
| Model | Capacity | Topology | Efficiency | Runtime @ 50% |
|---|---|---|---|---|
| CyberPower PR2000RTXL2U | 2,000 VA / 2,000 W | Line Interactive | 98.0% | 13 min |
| Delta RT-2K | 2,000 VA / 1,800 W | Double Conversion | 92.2% | 12 min |
| Liebert GXT5-2000LVRT2UXL | 2,000 VA / 1,800 W | Multi-Mode Double Conversion | 92.5% | 9 min |
| Vertiv GXT5-2000LVRT2UXL | 2,000 VA / 1,800 W | Multi-Mode Double Conversion | 92.5% | 9 min |
| Eaton 9PX2000RT | 2,000 VA / 1,800 W | Double Conversion | 92.5% | 20 min |
| CyberPower OR2200PFCRT2U | 2,000 VA / 1,540 W | Line Interactive | 98.2% | 13 min |
Panduit
More Panduit UPS battery backups
| Model | Capacity | Topology | Efficiency | Runtime @ 50% |
|---|---|---|---|---|
| 1A1V1A | 1,000 VA / 1,000 W | Multi-Mode Line Interactive | 90.9% | - |
| 1F1L1A, 1G1L1A, 1H1L1A | 5,000 VA / 5,000 W | Passive Standby | 94.5% | 24 min |
| 1F1V1A | 5,000 VA / 4,500 W | Multi-Mode Line Interactive | 93.6% | - |
| U01N14L | 1,000 VA / 900 W | Multi-Mode Double Conversion | 91.1% | 20 min |
| U01N16L-N | 1,000 VA / 900 W | Multi-Mode Double Conversion | 90.9% | 240 min |
| U02N14L | 2,000 VA / 1,800 W | Multi-Mode Double Conversion | 92.2% | 20 min |
| U03N14L | 3,000 VA / 2,700 W | Multi-Mode Double Conversion | 92.0% | 20 min |
| U03N15L | 3,000 VA / 2,700 W | Multi-Mode Double Conversion | 93.2% | 20 min |