Skip to content

UPS battery backupsENERGY STAR certified

Liebert GXT5-3000IRT2UXL

3,000 VA / 3,000 W multi-mode double conversion UPS.

Capacity

3,000 VA

3,000 W real power

Topology

Multi-Mode Double Conversion

Efficiency

93.6%

weighted, as tested

Runtime @ 50%

9 min

3 min at full load

A UPS has two ratings and the lower one is the limit. This unit is rated 3,000 VA and 3,000 W, so the equipment plugged into its battery outlets should draw no more than about 2,400 W if you want the usual 20% headroom. How to size a UPS.

Its weighted efficiency of 93.6% compares with a median of 93.1% across 95 certified units within 25% of its capacity. With nothing plugged in it still draws 31.9 W, about $36 a year at 13¢/kWh just to stand ready.

Maker
Liebert
Model
GXT5-3000IRT2UXL
Apparent power rating
3,000 VA
Real power rating
3,000 W
Power factor
1.00
Topology
Multi-Mode Double Conversion
Intended use
Consumer, Commercial, Data Center
Battery
Valve Regulated Lead-acid Battery
Runtime at 50% load
9 min
Runtime at 100% load
3 min
Battery warranty
2 yr
Weighted efficiency
93.6%
Efficiency at 25 / 50 / 75 / 100% load
92.3% / 93.6% / 93.7% / 93.4%
Input power at no load
31.9 W
Rack mountable
Yes
Rated input voltage
200-240 V
Rated output voltage
200-240 V
Connections
USB Port,Ethernet
Size (H x W x D)
85 x 430 x 540 mm
Maker take-back program
No
On the market since
Apr 2019
ENERGY STAR certified
1 Apr 2019

Certified under the same record

The maker lists these as the same machine or a variant of it: GXT5-3000IRT2UXLA, GXT5-3000IRT2UXLB, GXT5-3000IRT2UXLE, GXT5-3000IRT2UXLN, GXT5-3000IRT2UXLN_Liebert.

Source: ENERGY STAR certified uninterruptible power supplies dataset, US EPA, record 2336531, data build 2026-09-29. Figures are as the maker certified them. How we use this data.

Other makers

Machines comparable to the GXT5-3000IRT2UXL

Certified UPS units from other makers within 25% of its VA rating.

ModelCapacityTopologyEfficiencyRuntime @ 50%
CyberPower PR3000RTXL2UHVA3,000 VA / 3,000 WLine Interactive98.9%11 min
Delta RT-3K3,000 VA / 2,700 WDouble Conversion92.0%12 min
CyberPower OL3000RTXL2UHV3,000 VA / 2,700 WDouble Conversion92.0%11 min
CyberPower OL3000RTXL2UHVN3,000 VA / 2,700 WDouble Conversion92.0%11 min
CyberPower OL3000RTXL2UHVTAA3,000 VA / 2,700 WDouble Conversion92.0%11 min
CyberPower OL3000RT JP3,000 VA / 2,700 WDouble Conversion91.5%11 min

Liebert

More Liebert UPS battery backups

ModelCapacityTopologyEfficiencyRuntime @ 50%
10B14763GG103450 kVA / 405 kWMulti-Mode Double Conversion97.2%30 min
10B14789GF103825 kVA / 743 kWMulti-Mode Double Conversion97.7%30 min
47SA040A[0|1|2|3][C|Y][0|F|H|M|G|L][0|1]10 kVA / 10 kWMulti-Mode Double Conversion94.2%34 min
47SA100A[0|1|2|3][C|Y][0|F|H|M|G|L][0|1]60 kVA / 60 kWMulti-Mode Double Conversion95.8%10 min
47SA120A[0|1|2|3][C|Y][0|F|H|M|G|L][0|1]120 kVA / 120 kWMulti-Mode Double Conversion95.6%10 min
51SA030QAA30 kVA / 30 kWMulti-Mode Double Conversion96.3%10 min
51SA030QBA30 kVA / 30 kWMulti-Mode Double Conversion95.2%10 min
51SA050BAA50 kVA / 50 kWMulti-Mode Double Conversion96.4%10 min

All Liebert UPS battery backups