Skip to content

UPS battery backupsENERGY STAR certified

Vertiv ITA-10k00ALA102P00

10 kVA / 10 kW multi-mode double conversion UPS.

Capacity

10 kVA

10 kW real power

Topology

Multi-Mode Double Conversion

Efficiency

95.6%

weighted, as tested

Runtime @ 50%

63 min

23 min at full load

A UPS has two ratings and the lower one is the limit. This unit is rated 10 kVA and 10 kW, so the equipment plugged into its battery outlets should draw no more than about 8,000 W if you want the usual 20% headroom. How to size a UPS.

Its weighted efficiency of 95.6% compares with a median of 95.1% across 62 certified units within 25% of its capacity. With nothing plugged in it still draws 55.0 W, about $63 a year at 13¢/kWh just to stand ready.

Maker
Vertiv
Model
ITA-10k00ALA102P00
Apparent power rating
10 kVA
Real power rating
10 kW
Power factor
1.00
Topology
Multi-Mode Double Conversion
Intended use
Consumer, Commercial, Data Center
Battery
Valve Regulated Lead-acid Battery
Runtime at 50% load
63 min
Runtime at 100% load
23 min
Battery warranty
2 yr
Weighted efficiency
95.6%
Efficiency at 25 / 50 / 75 / 100% load
93.9% / 95.6% / 95.8% / 95.2%
Input power at no load
55.0 W
Rack mountable
Yes
Rated input voltage
380-415 V
Rated output voltage
220-240 V
Connections
USB Port,Ethernet
Size (H x W x D)
85 x 430 x 500 mm
Maker take-back program
No
On the market since
Apr 2017
ENERGY STAR certified
25 Dec 2018

Certified under the same record

The maker lists these as the same machine or a variant of it: ITA-10k00AEA102C00, ITA-10k00AEA102P00, ITA-10k00ALA102C00.

Source: ENERGY STAR certified uninterruptible power supplies dataset, US EPA, record 2332044, data build 2026-09-29. Figures are as the maker certified them. How we use this data.

Other makers

Machines comparable to the ITA-10k00ALA102P00

Certified UPS units from other makers within 25% of its VA rating.

ModelCapacityTopologyEfficiencyRuntime @ 50%
Delta RT-10K10 kVA / 10 kWDouble Conversion95.2%12 min
Liebert GXT5-10KIRT5UXLN10 kVA / 10 kWMulti-Mode Double Conversion95.1%7 min
Liebert GXE-10k00TLA102C0010 kVA / 9,000 WMulti-Mode Double Conversion95.5%19 min
Liebert GXT5-10KMVRT6UXLN10 kVA / 10 kWMulti-Mode Double Conversion93.9%9 min
Liebert GXT4-10000RT23010 kVA / 9,000 WMulti-Mode Double Conversion93.2%10 min
Liebert ITA-10k00ALA102P0010 kVA / 10 kWMulti-Mode Double Conversion95.6%63 min

Vertiv

More Vertiv UPS battery backups

ModelCapacityTopologyEfficiencyRuntime @ 50%
10B14763GG103450 kVA / 405 kWMulti-Mode Double Conversion97.2%30 min
10B14789GF103825 kVA / 743 kWMulti-Mode Double Conversion97.7%30 min
47SA040A[0|1|2|3][C|Y][0|F|H|M|G|L][0|1]10 kVA / 10 kWMulti-Mode Double Conversion94.2%34 min
47SA100A[0|1|2|3][C|Y][0|F|H|M|G|L][0|1]60 kVA / 60 kWMulti-Mode Double Conversion95.8%10 min
47SA120A[0|1|2|3][C|Y][0|F|H|M|G|L][0|1]120 kVA / 120 kWMulti-Mode Double Conversion95.6%10 min
51SA030QAA30 kVA / 30 kWMulti-Mode Double Conversion96.3%10 min
51SA030QBA30 kVA / 30 kWMulti-Mode Double Conversion95.2%10 min
51SA050BAA50 kVA / 50 kWMulti-Mode Double Conversion96.4%10 min

All Vertiv UPS battery backups