Skip to content

Delta UPS, ENERGY STAR certified

Delta RT-20K3P

20 kVA / 20 kW double conversion UPS.

Capacity

20 kVA

20 kW real power

Topology

Double Conversion

Efficiency

95.7%

weighted, as tested

Runtime @ 50%

10 min

3 min at full load

A UPS has two ratings and the lower one is the limit. This unit is rated 20 kVA and 20 kW, so the equipment plugged into its battery outlets should draw no more than about 16 kW if you want the usual 20% headroom. How to size a UPS.

Its weighted efficiency of 95.7% compares with a median of 95.5% across 45 certified units within 25% of its capacity. With nothing plugged in it still draws 189.3 W, about $216 a year at 13¢/kWh just to stand ready.

Maker
Delta
Model
RT-20K3P
Apparent power rating
20 kVA
Real power rating
20 kW
Power factor
1.00
Topology
Double Conversion
Intended use
Consumer, Commercial, Data Center
Battery
Valve Regulated Lead-acid Battery
Runtime at 50% load
10 min
Runtime at 100% load
3 min
Battery warranty
3 yr
Weighted efficiency
95.7%
Efficiency at 25 / 50 / 75 / 100% load
95.0% / 96.0% / 96.0% / 95.9%
Input power at no load
189.3 W
Rack mountable
Yes
Rated input voltage
220-240 V
Rated output voltage
220-240 V
Connections
Serial Port,Ethernet,USB Port
Size (H x W x D)
88 x 440 x 730 mm
Maker take-back program
No
On the market since
Jul 2019
ENERGY STAR certified
27 Jun 2019

Certified under the same record

The maker lists these as the same machine or a variant of it: Lithium-ion Battery.

Source: ENERGY STAR certified uninterruptible power supplies dataset, US EPA, record 2340464, data build 2026-09-29. Figures are as the maker certified them. How we use this data.

Other makers

Machines comparable to the RT-20K3P

Certified UPS units from other makers within 25% of its VA rating.

ModelCapacityTopologyEfficiencyRuntime @ 50%
Schneider Electric Galaxy VS 30kW 480V w/o Batteries, Start-up 5x820 kVA / 20 kWMulti-Mode Double Conversion95.9%-
Schneider Electric GVSUPS80KGS20 kVA / 20 kWMulti-Mode Double Conversion95.9%-
Schneider Electric Galaxy VS 40kW 480V w/o Batteries, Start-up 5x820 kVA / 20 kWMulti-Mode Double Conversion95.9%-
Schneider Electric Galaxy VS 20kW 480V w/o Batteries, Start-up 5x820 kVA / 20 kWMulti-Mode Double Conversion95.9%-
Schneider Electric Galaxy VS 50kW 480V w/o Batteries, Start-up 5x820 kVA / 20 kWMulti-Mode Double Conversion95.9%-
Schneider Electric Galaxy VS 100kW 480V w/o Batteries, Start-up 5x820 kVA / 20 kWMulti-Mode Double Conversion95.9%-

Delta

More Delta UPS battery backups

ModelCapacityTopologyEfficiencyRuntime @ 50%
DPH-105K-LV15 kVA / 15 kWMulti-Mode Double Conversion95.6%-
DPH-150K-HV50 kVA / 50 kWMulti-Mode Double Conversion96.3%23 min
DPH-250K-HV250 kVA / 250 kWMulti-Mode Double Conversion94.9%10 min
DPH-300K-HV50 kVA / 50 kWMulti-Mode Double Conversion96.3%12 min
DPH-500K-HV200 kVA / 200 kWMulti-Mode Double Conversion99.1%11 min
DPH-60K-LV15 kVA / 15 kWMulti-Mode Double Conversion95.5%12 min
RT PRO-1K1,000 VA / 1,000 WMulti-Mode Double Conversion91.4%10 min
RT PRO-2K2,000 VA / 2,000 WMulti-Mode Double Conversion93.4%12 min

All Delta UPS battery backups