Delta RT-10K3P

10 kVA / 10 kW double conversion UPS.

Capacity

10 kVA

10 kW real power

Topology

Double Conversion

Efficiency

95.6%

weighted, as tested

Runtime @ 50%

7 min

3 min at full load

A UPS has two ratings and the lower one is the limit. This unit is rated 10 kVA and 10 kW, so the equipment plugged into its battery outlets should draw no more than about 8,000 W if you want the usual 20% headroom. How to size a UPS.

Its weighted efficiency of 95.6% compares with a median of 95.1% across 62 certified units within 25% of its capacity. With nothing plugged in it still draws 0.7 W, about $0.84 a year at 13¢/kWh just to stand ready.

Maker
Delta
Model
RT-10K3P
Apparent power rating
10 kVA
Real power rating
10 kW
Power factor
1.00
Topology
Double Conversion
Intended use
Commercial, Data Center
Runtime at 50% load
7 min
Runtime at 100% load
3 min
Battery warranty
3 yr
Weighted efficiency
95.6%
Efficiency at 25 / 50 / 75 / 100% load
94.6% / 95.6% / 95.7% / 95.5%
Input power at no load
0.7 W
Rack mountable
No
Modular
Yes
Rated input voltage
380-415 V
Rated output voltage
380-415 V
Connections
Ethernet,USB Port
Size (H x W x D)
84 x 440 x 535 mm
Maker take-back program
No
On the market since
Jun 2021
ENERGY STAR certified
24 Feb 2021

Source: ENERGY STAR certified uninterruptible power supplies dataset, US EPA, record 2376192, data build 2026-09-29. Figures are as the maker certified them. How we use this data.

Other makers

Machines comparable to the RT-10K3P

Certified UPS units from other makers within 25% of its VA rating.

ModelCapacityTopologyEfficiencyRuntime @ 50%
Liebert GXT5-10KIRT5UXLN10 kVA / 10 kWMulti-Mode Double Conversion95.1%7 min
Vertiv GXT5-10KIRT5UXLN10 kVA / 10 kWMulti-Mode Double Conversion95.1%7 min
Liebert GXE-10k00TLA102C0010 kVA / 9,000 WMulti-Mode Double Conversion95.5%19 min
Vertiv GXE-10k00TLA102C0010 kVA / 9,000 WMulti-Mode Double Conversion95.5%19 min
Liebert GXT5-10KMVRT6UXLN10 kVA / 10 kWMulti-Mode Double Conversion93.9%9 min
Vertiv GXT5-10KMVRT6UXLN10 kVA / 10 kWMulti-Mode Double Conversion93.9%9 min

Delta

More Delta UPS battery backups

ModelCapacityTopologyEfficiencyRuntime @ 50%
DPH-105K-LV15 kVA / 15 kWMulti-Mode Double Conversion95.6%-
DPH-150K-HV50 kVA / 50 kWMulti-Mode Double Conversion96.3%23 min
DPH-250K-HV250 kVA / 250 kWMulti-Mode Double Conversion94.9%10 min
DPH-300K-HV50 kVA / 50 kWMulti-Mode Double Conversion96.3%12 min
DPH-500K-HV200 kVA / 200 kWMulti-Mode Double Conversion99.1%11 min
DPH-60K-LV15 kVA / 15 kWMulti-Mode Double Conversion95.5%12 min
RT PRO-1K1,000 VA / 1,000 WMulti-Mode Double Conversion91.4%10 min
RT PRO-2K2,000 VA / 2,000 WMulti-Mode Double Conversion93.4%12 min

All Delta UPS battery backups