Skip to content

UPS battery backupsENERGY STAR certified

Schneider Electric GVSUPS60K0B5GS

60 kVA / 60 kW multi-mode double conversion UPS.

Galaxy VS UPS 60kW 480V for up to 5 internal 9Ah smart modular battery strings, Start-up 5x8

Capacity

60 kVA

60 kW real power

Topology

Multi-Mode Double Conversion

Efficiency

96.1%

weighted, as tested

Runtime @ 50%

-

not reported by the maker

A UPS has two ratings and the lower one is the limit. This unit is rated 60 kVA and 60 kW, so the equipment plugged into its battery outlets should draw no more than about 48 kW if you want the usual 20% headroom. How to size a UPS.

Its weighted efficiency of 96.1% compares with a median of 96.3% across 27 certified units within 25% of its capacity. With nothing plugged in it still draws 365.6 W, about $416 a year at 13¢/kWh just to stand ready.

Maker
Schneider Electric
Model
GVSUPS60K0B5GS
Description
Galaxy VS UPS 60kW 480V for up to 5 internal 9Ah smart modular battery strings, Start-up 5x8
Apparent power rating
60 kVA
Real power rating
60 kW
Power factor
1.00
Topology
Multi-Mode Double Conversion
Intended use
Data Center
Battery
Valve Regulated Lead-acid Battery
Weighted efficiency
96.1%
Efficiency at 25 / 50 / 75 / 100% load
95.3% / 96.3% / 96.5% / 96.5%
Input power at no load
365.6 W
Rack mountable
No
Rated input voltage
480 V
Rated output voltage
480 V
Connections
Serial Port,Ethernet
Size (H x W x D)
1970 x 550 x 847 mm
Maker take-back program
Yes
On the market since
Feb 2020
ENERGY STAR certified
5 Mar 2020

Source: ENERGY STAR certified uninterruptible power supplies dataset, US EPA, record 2355965, data build 2026-09-29. Figures are as the maker certified them. How we use this data.

Other makers

Machines comparable to the GVSUPS60K0B5GS

Certified UPS units from other makers within 25% of its VA rating.

ModelCapacityTopologyEfficiencyRuntime @ 50%
Vertiv Liebert EXS Fr3 series60 kVA / 60 kWMulti-Mode Double Conversion95.4%20 min
Liebert EXS Fr3 series60 kVA / 60 kWMulti-Mode Double Conversion95.4%20 min
Liebert 47SA100A[0|1|2|3][C|Y][0|F|H|M|G|L][0|1]60 kVA / 60 kWMulti-Mode Double Conversion95.8%10 min
Vertiv 47SA100A[0|1|2|3][C|Y][0|F|H|M|G|L][0|1]60 kVA / 60 kWMulti-Mode Double Conversion95.8%10 min
Vertiv Liebert APM2 FR3 c2 Series60 kVA / 60 kWMulti-Mode Double Conversion97.0%40 min
Liebert APM2 FR3 c2 Series60 kVA / 60 kWMulti-Mode Double Conversion97.0%40 min

Schneider Electric

More Schneider Electric UPS battery backups

ModelCapacityTopologyEfficiencyRuntime @ 50%
Galaxy VL UPS 500 kW 400/480V Start-up 5x8200 kVA / 200 kWMulti-Mode Double Conversion96.9%-
Galaxy VM 160 kVA UPS Parallel 480-480 V, 65kAIC160 kVA / 144 kWDouble Conversion96.8%-
Galaxy VM 160 kVA UPS Single 480-480 V, 65kAIC,160 kVA / 144 kWDouble Conversion96.8%-
Galaxy VM 180 kVA UPS Parallel 480-480 V, 65kAIC180 kVA / 162 kWDouble Conversion96.9%-
Galaxy VM 180 kVA UPS Single 480-480 V, 65kAIC180 kVA / 162 kWDouble Conversion96.9%-
Galaxy VM 225 kVA UPS Parallel 480-480 V, 65kAIC225 kVA / 202.5 kWDouble Conversion97.0%-
Galaxy VM 225 kVA UPS Single 480-480 V, 65kAIC,225 kVA / 202.5 kWDouble Conversion97.0%-
Galaxy VS 100kW 480V w/o Batteries, Start-up 5x820 kVA / 20 kWMulti-Mode Double Conversion95.9%-

All Schneider Electric UPS battery backups