Skip to content

UPS battery backupsENERGY STAR certified

Schneider Electric GVSUPS120KGS

120 kVA / 120 kW multi-mode double conversion UPS.

Galaxy VS 120kW 480V without Batteries, Start-up 5x8

Capacity

120 kVA

120 kW real power

Topology

Multi-Mode Double Conversion

Efficiency

97.0%

weighted, as tested

Runtime @ 50%

-

not reported by the maker

A UPS has two ratings and the lower one is the limit. This unit is rated 120 kVA and 120 kW, so the equipment plugged into its battery outlets should draw no more than about 96 kW if you want the usual 20% headroom. How to size a UPS.

Its weighted efficiency of 97.0% compares with a median of 96.0% across 6 certified units within 25% of its capacity. With nothing plugged in it still draws 554.8 W, about $632 a year at 13¢/kWh just to stand ready.

Maker
Schneider Electric
Model
GVSUPS120KGS
Description
Galaxy VS 120kW 480V without Batteries, Start-up 5x8
Apparent power rating
120 kVA
Real power rating
120 kW
Power factor
1.00
Topology
Multi-Mode Double Conversion
Intended use
Data Center
Battery
Valve Regulated Lead-acid Battery
Weighted efficiency
97.0%
Efficiency at 25 / 50 / 75 / 100% load
96.3% / 97.1% / 97.3% / 97.2%
Input power at no load
554.8 W
Rack mountable
No
Rated input voltage
480 V
Rated output voltage
480 V
Connections
Serial Port,Ethernet
Size (H x W x D)
1485 x 521 x 847 mm
Maker take-back program
Yes
On the market since
Mar 2021
ENERGY STAR certified
24 Feb 2021

Certified under the same record

The maker lists these as the same machine or a variant of it: Galaxy VS 120kW 480V without Batteries, GVSUPS120KG.

Source: ENERGY STAR certified uninterruptible power supplies dataset, US EPA, record 2375506, data build 2026-09-29. Figures are as the maker certified them. How we use this data.

Other makers

Machines comparable to the GVSUPS120KGS

Certified UPS units from other makers within 25% of its VA rating.

ModelCapacityTopologyEfficiencyRuntime @ 50%
Liebert 47SA120A[0|1|2|3][C|Y][0|F|H|M|G|L][0|1]120 kVA / 120 kWMulti-Mode Double Conversion95.6%10 min
Vertiv 47SA120A[0|1|2|3][C|Y][0|F|H|M|G|L][0|1]120 kVA / 120 kWMulti-Mode Double Conversion95.6%10 min
Liebert eXM 0120kTK16FN01000120 kVA / 120 kWMulti-Mode Double Conversion96.0%10 min
Vertiv eXM 0120kTK16FN01000120 kVA / 120 kWMulti-Mode Double Conversion96.0%10 min
Eaton S3M100K100 kVA / 100 kWDouble Conversion96.1%-

Schneider Electric

More Schneider Electric UPS battery backups

ModelCapacityTopologyEfficiencyRuntime @ 50%
Galaxy VL UPS 500 kW 400/480V Start-up 5x8200 kVA / 200 kWMulti-Mode Double Conversion96.9%-
Galaxy VM 160 kVA UPS Parallel 480-480 V, 65kAIC160 kVA / 144 kWDouble Conversion96.8%-
Galaxy VM 160 kVA UPS Single 480-480 V, 65kAIC,160 kVA / 144 kWDouble Conversion96.8%-
Galaxy VM 180 kVA UPS Parallel 480-480 V, 65kAIC180 kVA / 162 kWDouble Conversion96.9%-
Galaxy VM 180 kVA UPS Single 480-480 V, 65kAIC180 kVA / 162 kWDouble Conversion96.9%-
Galaxy VM 225 kVA UPS Parallel 480-480 V, 65kAIC225 kVA / 202.5 kWDouble Conversion97.0%-
Galaxy VM 225 kVA UPS Single 480-480 V, 65kAIC,225 kVA / 202.5 kWDouble Conversion97.0%-
Galaxy VS 100kW 480V w/o Batteries, Start-up 5x820 kVA / 20 kWMulti-Mode Double Conversion95.9%-

All Schneider Electric UPS battery backups