160 kVA / 144 kW double conversion UPS.
Galaxy VM 160 kVA Additional UPS for 1+1 480-480 V
Capacity
160 kVA
144 kW real power
Topology
Double Conversion
Efficiency
96.8%
weighted, as tested
Runtime @ 50%
-
not reported by the maker
A UPS has two ratings and the lower one is the limit. This unit is rated 160 kVA and 144 kW, so the equipment plugged into its battery outlets should draw no more than about 115.2 kW if you want the usual 20% headroom. How to size a UPS.
Its weighted efficiency of 96.8% compares with a median of 96.8% across 23 certified units within 25% of its capacity. With nothing plugged in it still draws 1,072.0 W, about $1,221 a year at 13¢/kWh just to stand ready.
- Maker
- Schneider Electric
- Model
- GVMRB160KG65S
- Description
- Galaxy VM 160 kVA Additional UPS for 1+1 480-480 V
- Apparent power rating
- 160 kVA
- Real power rating
- 144 kW
- Power factor
- 0.90
- Topology
- Double Conversion
- Intended use
- Data Center
- Battery
- Valve Regulated Lead-acid Battery
- Weighted efficiency
- 96.8%
- Efficiency at 25 / 50 / 75 / 100% load
- 95.1% / 96.4% / 96.5% / 96.4%
- Input power at no load
- 1,072.0 W
- Rack mountable
- No
- Rated input voltage
- 480 V
- Rated output voltage
- 480 V
- Connections
- Serial Port,Ethernet
- Size (H x W x D)
- 1970 x 1002 x 854 mm
- Maker take-back program
- Yes
- On the market since
- Sep 2015
- ENERGY STAR certified
- 26 Feb 2019
Certified under the same record
The maker lists these as the same machine or a variant of it: GVMRB160KGS.
Source: ENERGY STAR certified uninterruptible power supplies dataset, US EPA, record 2333997, data build 2026-09-29. Figures are as the maker certified them. How we use this data.
Other makers
Machines comparable to the GVMRB160KG65S
Certified UPS units from other makers within 25% of its VA rating.
| Model | Capacity | Topology | Efficiency | Runtime @ 50% |
|---|---|---|---|---|
| Liebert eXM 0160kTK16FN01000 | 160 kVA / 160 kW | Multi-Mode Double Conversion | 96.1% | 10 min |
| Vertiv eXM 0160kTK16FN01000 | 160 kVA / 160 kW | Multi-Mode Double Conversion | 96.1% | 10 min |
| NEUROPOWER GALLEON PRO III 180KS | 180 kVA / 180 kW | Double Conversion | 96.4% | - |
| Liebert 47SA120A[0|1|2|3][C|Y][0|F|H|M|G|L][0|1] | 120 kVA / 120 kW | Multi-Mode Double Conversion | 95.6% | 10 min |
| Vertiv 47SA120A[0|1|2|3][C|Y][0|F|H|M|G|L][0|1] | 120 kVA / 120 kW | Multi-Mode Double Conversion | 95.6% | 10 min |
| Liebert 51SA200LAA | 200 kVA / 200 kW | Multi-Mode Double Conversion | 96.5% | 10 min |
Schneider Electric
More Schneider Electric UPS battery backups
| Model | Capacity | Topology | Efficiency | Runtime @ 50% |
|---|---|---|---|---|
| Galaxy VL UPS 500 kW 400/480V Start-up 5x8 | 200 kVA / 200 kW | Multi-Mode Double Conversion | 96.9% | - |
| Galaxy VM 160 kVA UPS Parallel 480-480 V, 65kAIC | 160 kVA / 144 kW | Double Conversion | 96.8% | - |
| Galaxy VM 160 kVA UPS Single 480-480 V, 65kAIC, | 160 kVA / 144 kW | Double Conversion | 96.8% | - |
| Galaxy VM 180 kVA UPS Parallel 480-480 V, 65kAIC | 180 kVA / 162 kW | Double Conversion | 96.9% | - |
| Galaxy VM 180 kVA UPS Single 480-480 V, 65kAIC | 180 kVA / 162 kW | Double Conversion | 96.9% | - |
| Galaxy VM 225 kVA UPS Parallel 480-480 V, 65kAIC | 225 kVA / 202.5 kW | Double Conversion | 97.0% | - |
| Galaxy VM 225 kVA UPS Single 480-480 V, 65kAIC, | 225 kVA / 202.5 kW | Double Conversion | 97.0% | - |
| Galaxy VS 100kW 480V w/o Batteries, Start-up 5x8 | 20 kVA / 20 kW | Multi-Mode Double Conversion | 95.9% | - |