UPS battery backupsENERGY STAR certified
Schneider Electric Galaxy VS 60kW 480V w/o Batteries, Start-up 5x8
60 kVA / 60 kW multi-mode double conversion UPS, model number GVSUPS60KGS.
Capacity
60 kVA
60 kW real power
Topology
Multi-Mode Double Conversion
Efficiency
96.8%
weighted, as tested
Runtime @ 50%
-
not reported by the maker
A UPS has two ratings and the lower one is the limit. This unit is rated 60 kVA and 60 kW, so the equipment plugged into its battery outlets should draw no more than about 48 kW if you want the usual 20% headroom. How to size a UPS.
Its weighted efficiency of 96.8% compares with a median of 96.3% across 27 certified units within 25% of its capacity. With nothing plugged in it still draws 348.8 W, about $397 a year at 13¢/kWh just to stand ready.
- Maker
- Schneider Electric
- Model
- Galaxy VS 60kW 480V w/o Batteries, Start-up 5x8
- Model number
- GVSUPS60KGS
- Apparent power rating
- 60 kVA
- Real power rating
- 60 kW
- Power factor
- 1.00
- Topology
- Multi-Mode Double Conversion
- Intended use
- Data Center
- Battery
- Valve Regulated Lead-acid Battery
- Weighted efficiency
- 96.8%
- Efficiency at 25 / 50 / 75 / 100% load
- 95.9% / 97.0% / 97.3% / 97.3%
- Input power at no load
- 348.8 W
- Rack mountable
- No
- Rated input voltage
- 480 V
- Rated output voltage
- 480 V
- Connections
- Serial Port,Ethernet
- Size (H x W x D)
- 1485 x 521 x 847 mm
- Maker take-back program
- Yes
- On the market since
- Mar 2021
- ENERGY STAR certified
- 27 Jul 2018
Certified under the same record
The maker lists these as the same machine or a variant of it: Galaxy VS 60kW 480V without Batteries, GVSUPS60KG.
Source: ENERGY STAR certified uninterruptible power supplies dataset, US EPA, record 2325818, data build 2026-09-29. Figures are as the maker certified them. How we use this data.
Other makers
Machines comparable to the Galaxy VS 60kW 480V w/o Batteries, Start-up 5x8
Certified UPS units from other makers within 25% of its VA rating.
| Model | Capacity | Topology | Efficiency | Runtime @ 50% |
|---|---|---|---|---|
| Vertiv Liebert EXS Fr3 series | 60 kVA / 60 kW | Multi-Mode Double Conversion | 95.4% | 20 min |
| Liebert EXS Fr3 series | 60 kVA / 60 kW | Multi-Mode Double Conversion | 95.4% | 20 min |
| Liebert 47SA100A[0|1|2|3][C|Y][0|F|H|M|G|L][0|1] | 60 kVA / 60 kW | Multi-Mode Double Conversion | 95.8% | 10 min |
| Vertiv 47SA100A[0|1|2|3][C|Y][0|F|H|M|G|L][0|1] | 60 kVA / 60 kW | Multi-Mode Double Conversion | 95.8% | 10 min |
| Vertiv Liebert APM2 FR3 c2 Series | 60 kVA / 60 kW | Multi-Mode Double Conversion | 97.0% | 40 min |
| Liebert APM2 FR3 c2 Series | 60 kVA / 60 kW | Multi-Mode Double Conversion | 97.0% | 40 min |
Schneider Electric
More Schneider Electric UPS battery backups
| Model | Capacity | Topology | Efficiency | Runtime @ 50% |
|---|---|---|---|---|
| Galaxy VL UPS 500 kW 400/480V Start-up 5x8 | 200 kVA / 200 kW | Multi-Mode Double Conversion | 96.9% | - |
| Galaxy VM 160 kVA UPS Parallel 480-480 V, 65kAIC | 160 kVA / 144 kW | Double Conversion | 96.8% | - |
| Galaxy VM 160 kVA UPS Single 480-480 V, 65kAIC, | 160 kVA / 144 kW | Double Conversion | 96.8% | - |
| Galaxy VM 180 kVA UPS Parallel 480-480 V, 65kAIC | 180 kVA / 162 kW | Double Conversion | 96.9% | - |
| Galaxy VM 180 kVA UPS Single 480-480 V, 65kAIC | 180 kVA / 162 kW | Double Conversion | 96.9% | - |
| Galaxy VM 225 kVA UPS Parallel 480-480 V, 65kAIC | 225 kVA / 202.5 kW | Double Conversion | 97.0% | - |
| Galaxy VM 225 kVA UPS Single 480-480 V, 65kAIC, | 225 kVA / 202.5 kW | Double Conversion | 97.0% | - |
| Galaxy VS 100kW 480V w/o Batteries, Start-up 5x8 | 20 kVA / 20 kW | Multi-Mode Double Conversion | 95.9% | - |