UPS battery backupsENERGY STAR certified
Eaton SUINT1500LCD2U
1,500 VA / 1,500 W double conversion UPS.
Capacity
1,500 VA
1,500 W real power
Topology
Double Conversion
Efficiency
92.0%
weighted, as tested
Runtime @ 50%
9 min
4 min at full load
A UPS has two ratings and the lower one is the limit. This unit is rated 1,500 VA and 1,500 W, so the equipment plugged into its battery outlets should draw no more than about 1,200 W if you want the usual 20% headroom. How to size a UPS.
Its weighted efficiency of 92.0% compares with a median of 98.7% across 153 certified units within 25% of its capacity. With nothing plugged in it still draws 50.7 W, about $58 a year at 13¢/kWh just to stand ready.
- Maker
- Eaton
- Model
- SUINT1500LCD2U
- Apparent power rating
- 1,500 VA
- Real power rating
- 1,500 W
- Power factor
- 1.00
- Topology
- Double Conversion
- Intended use
- Consumer, Commercial, Data Center
- Battery
- Other
- Runtime at 50% load
- 9 min
- Runtime at 100% load
- 4 min
- Battery warranty
- 2 yr
- Weighted efficiency
- 92.0%
- Efficiency at 25 / 50 / 75 / 100% load
- 88.2% / 90.7% / 92.5% / 92.3%
- Input power at no load
- 50.7 W
- Rack mountable
- Yes, 2U
- Rated input voltage
- 200-240 V
- Rated output voltage
- 200-240 V
- Connections
- Other
- Size (H x W x D)
- 86 x 440 x 450 mm
- Maker take-back program
- No
- On the market since
- Nov 2024
- ENERGY STAR certified
- 12 Dec 2022
Certified under the same record
The maker lists these as the same machine or a variant of it: SUINT1500LCD2UAM.
Source: ENERGY STAR certified uninterruptible power supplies dataset, US EPA, record 2405637, data build 2026-09-29. Figures are as the maker certified them. How we use this data.
Other makers
Machines comparable to the SUINT1500LCD2U
Certified UPS units from other makers within 25% of its VA rating.
| Model | Capacity | Topology | Efficiency | Runtime @ 50% |
|---|---|---|---|---|
| CyberPower PR1500RTXL2U | 1,500 VA / 1,500 W | Line Interactive | 98.5% | 19 min |
| CyberPower CP1500AVRTa | 1,500 VA / 900 W | Line Interactive | 98.8% | 12 min |
| APC BX1500M | 1,500 VA / 900 W | Line Interactive | 98.9% | 11 min |
| Delta RT-1.5K | 1,500 VA / 1,350 W | Double Conversion | 91.2% | 12 min |
| CyberPower OL1500RT JP | 1,500 VA / 1,350 W | Double Conversion | 90.9% | 11 min |
| CyberPower OL1500RTN JP | 1,500 VA / 1,350 W | Double Conversion | 90.9% | 11 min |
Eaton
More Eaton UPS battery backups
| Model | Capacity | Topology | Efficiency | Runtime @ 50% |
|---|---|---|---|---|
| 5P1000RT2UG2-L | 1,000 VA / 920 W | Line Interactive | 98.6% | 18 min |
| 5P1150IRT2UG2-L | 1,150 VA / 920 W | Line Interactive | 98.5% | 18 min |
| 5P1550IRT2UG2-L | 1,550 VA / 1,350 W | Line Interactive | 98.9% | 12 min |
| 5P1550RT2UG2-L | 1,440 VA / 1,350 W | Line Interactive | 98.7% | 12 min |
| 5P550RG2-L | 550 VA / 495 W | Line Interactive | 98.5% | 18 min |
| 5P650IRG2-L | 650 VA / 520 W | Line Interactive | 98.4% | 16 min |
| 5PX1000IRT2UG2 | 1,000 VA / 1,000 W | Line Interactive | 98.5% | 17 min |
| 5PX1000RTG2 | 1,000 VA / 1,000 W | Line Interactive | 98.5% | 16 min |