Eaton UPS, ENERGY STAR certified
Eaton S3M20K3B
20 kVA / 20 kW double conversion UPS.
Capacity
20 kVA
20 kW real power
Topology
Double Conversion
Efficiency
95.2%
weighted, as tested
Runtime @ 50%
16 min
7 min at full load
A UPS has two ratings and the lower one is the limit. This unit is rated 20 kVA and 20 kW, so the equipment plugged into its battery outlets should draw no more than about 16 kW if you want the usual 20% headroom. How to size a UPS.
Its weighted efficiency of 95.2% compares with a median of 95.6% across 45 certified units within 25% of its capacity.
- Maker
- Eaton
- Model
- S3M20K3B
- Apparent power rating
- 20 kVA
- Real power rating
- 20 kW
- Power factor
- 1.00
- Topology
- Double Conversion
- Intended use
- Consumer, Commercial, Data Center
- Battery
- Valve Regulated Lead-acid Battery
- Runtime at 50% load
- 16 min
- Runtime at 100% load
- 7 min
- Battery warranty
- 1 yr
- Weighted efficiency
- 95.2%
- Efficiency at 25 / 50 / 75 / 100% load
- 95.5% / 95.4% / 94.6% / 93.1%
- Rack mountable
- No
- Rated input voltage
- 208-220 V
- Rated output voltage
- 208-220 V
- Connections
- Serial Port,Other,Ethernet,USB Port
- Size (H x W x D)
- 868 x 250 x 900 mm
- Maker take-back program
- No
- On the market since
- Jun 2021
- ENERGY STAR certified
- 27 Jan 2026
Certified under the same record
The maker lists these as the same machine or a variant of it: S3M20K-NIB.
Source: ENERGY STAR certified uninterruptible power supplies dataset, US EPA, record 4576985, data build 2026-09-29. Figures are as the maker certified them. How we use this data.
Other makers
Machines comparable to the S3M20K3B
Certified UPS units from other makers within 25% of its VA rating.
| Model | Capacity | Topology | Efficiency | Runtime @ 50% |
|---|---|---|---|---|
| Schneider Electric Galaxy VS 30kW 480V w/o Batteries, Start-up 5x8 | 20 kVA / 20 kW | Multi-Mode Double Conversion | 95.9% | - |
| Schneider Electric GVSUPS80KGS | 20 kVA / 20 kW | Multi-Mode Double Conversion | 95.9% | - |
| Schneider Electric Galaxy VS 40kW 480V w/o Batteries, Start-up 5x8 | 20 kVA / 20 kW | Multi-Mode Double Conversion | 95.9% | - |
| Schneider Electric Galaxy VS 20kW 480V w/o Batteries, Start-up 5x8 | 20 kVA / 20 kW | Multi-Mode Double Conversion | 95.9% | - |
| Schneider Electric Galaxy VS 50kW 480V w/o Batteries, Start-up 5x8 | 20 kVA / 20 kW | Multi-Mode Double Conversion | 95.9% | - |
| Schneider Electric Galaxy VS 100kW 480V w/o Batteries, Start-up 5x8 | 20 kVA / 20 kW | Multi-Mode Double Conversion | 95.9% | - |
Eaton
More Eaton UPS battery backups
| Model | Capacity | Topology | Efficiency | Runtime @ 50% |
|---|---|---|---|---|
| 5P1000RT2UG2-L | 1,000 VA / 920 W | Line Interactive | 98.6% | 18 min |
| 5P1150IRT2UG2-L | 1,150 VA / 920 W | Line Interactive | 98.5% | 18 min |
| 5P1550IRT2UG2-L | 1,550 VA / 1,350 W | Line Interactive | 98.9% | 12 min |
| 5P1550RT2UG2-L | 1,440 VA / 1,350 W | Line Interactive | 98.7% | 12 min |
| 5P550RG2-L | 550 VA / 495 W | Line Interactive | 98.5% | 18 min |
| 5P650IRG2-L | 650 VA / 520 W | Line Interactive | 98.4% | 16 min |
| 5PX1000IRT2UG2 | 1,000 VA / 1,000 W | Line Interactive | 98.5% | 17 min |
| 5PX1000RTG2 | 1,000 VA / 1,000 W | Line Interactive | 98.5% | 16 min |