UPS battery backupsENERGY STAR certified
CyberPower PR5000LCDRTXL5U
5,000 VA / 4,500 W line interactive UPS.
Capacity
5,000 VA
4,500 W real power
Topology
Line Interactive
Efficiency
98.5%
weighted, as tested
Runtime @ 50%
28 min
10 min at full load
A UPS has two ratings and the lower one is the limit. This unit is rated 5,000 VA and 4,500 W, so the equipment plugged into its battery outlets should draw no more than about 3,600 W if you want the usual 20% headroom. How to size a UPS.
Its weighted efficiency of 98.5% compares with a median of 94.6% across 98 certified units within 25% of its capacity. With nothing plugged in it still draws 5.4 W, about $6.15 a year at 13¢/kWh just to stand ready.
- Maker
- CyberPower
- Model
- PR5000LCDRTXL5U
- Apparent power rating
- 5,000 VA
- Real power rating
- 4,500 W
- Power factor
- 0.90
- Topology
- Line Interactive
- Intended use
- Consumer, Commercial, Data Center
- Battery
- Valve Regulated Lead-acid Battery
- Runtime at 50% load
- 28 min
- Runtime at 100% load
- 10 min
- Battery warranty
- 3 yr
- Weighted efficiency
- 98.5%
- Efficiency at 25 / 50 / 75 / 100% load
- 98.8% / 98.7% / 98.5% / 98.3%
- Input power at no load
- 5.4 W
- Rack mountable
- Yes, 5U
- Rated input voltage
- 208-240 V
- Rated output voltage
- 208-240 V
- Connections
- Serial Port,USB Port,Ethernet
- Size (H x W x D)
- 433 x 220 x 645 mm
- Maker take-back program
- Yes
- On the market since
- Mar 2016
- ENERGY STAR certified
- 14 Jan 2019
Certified under the same record
The maker lists these as the same machine or a variant of it: PR5000LCDRTXL5UN, PR5000LCDRTXL5UNTAA, PR5000LCDRTXL5UTAA.
Source: ENERGY STAR certified uninterruptible power supplies dataset, US EPA, record 2333811, data build 2026-09-29. Figures are as the maker certified them. How we use this data.
Other makers
Machines comparable to the PR5000LCDRTXL5U
Certified UPS units from other makers within 25% of its VA rating.
| Model | Capacity | Topology | Efficiency | Runtime @ 50% |
|---|---|---|---|---|
| Tripp Lite AGPS7255 | 5,000 VA / 4,500 W | Double Conversion | 93.3% | 11 min |
| Eaton 9PX5K | 5,000 VA / 4,500 W | Double Conversion | 92.9% | 8 min |
| Liebert GXT4-5000RT230 | 5,000 VA / 4,000 W | Multi-Mode Double Conversion | 93.6% | 22 min |
| Vertiv GXT4-5000RT230 | 5,000 VA / 4,000 W | Multi-Mode Double Conversion | 93.6% | 22 min |
| Liebert GXT4-5000RT208 | 5,000 VA / 4,000 W | Multi-Mode Double Conversion | 92.2% | 17 min |
| Vertiv GXT4-5000RT208 | 5,000 VA / 4,000 W | Multi-Mode Double Conversion | 92.2% | 17 min |
CyberPower
More CyberPower UPS battery backups
| Model | Capacity | Topology | Efficiency | Runtime @ 50% |
|---|---|---|---|---|
| AVRG1000LCD | 1,000 VA / 530 W | Line Interactive | 98.6% | 10 min |
| BL1250U2 | 1,200 VA / 800 W | Line Interactive | 98.7% | 11 min |
| BL1450U | 1,200 VA / 800 W | Line Interactive | 98.7% | 11 min |
| BRG1000AVRLCD | 1,000 VA / 600 W | Line Interactive | 98.5% | 9 min |
| BRG1500AVRLCD | 1,500 VA / 900 W | Line Interactive | 98.6% | 12 min |
| BRG1500AVRLCD2 | 1,500 VA / 900 W | Line Interactive | 98.8% | 11 min |
| CP1000PFCLCD | 1,000 VA / 600 W | Line Interactive | 98.8% | 9 min |
| CP1000PFCLCDa | 1,000 VA / 600 W | Line Interactive | 99.3% | 8 min |