CyberPower UPS, ENERGY STAR certified
CyberPower OL3000RTXL2UNTAA
3,000 VA / 2,700 W double conversion UPS.
Capacity
3,000 VA
2,700 W real power
Topology
Double Conversion
Efficiency
91.5%
weighted, as tested
Runtime @ 50%
11 min
4 min at full load
A UPS has two ratings and the lower one is the limit. This unit is rated 3,000 VA and 2,700 W, so the equipment plugged into its battery outlets should draw no more than about 2,160 W if you want the usual 20% headroom. How to size a UPS.
Its weighted efficiency of 91.5% compares with a median of 93.1% across 95 certified units within 25% of its capacity. With nothing plugged in it still draws 46.9 W, about $53 a year at 13¢/kWh just to stand ready.
- Maker
- CyberPower
- Model
- OL3000RTXL2UNTAA
- Apparent power rating
- 3,000 VA
- Real power rating
- 2,700 W
- Power factor
- 0.90
- Topology
- Double Conversion
- Intended use
- Consumer, Commercial
- Battery
- Valve Regulated Lead-acid Battery
- Runtime at 50% load
- 11 min
- Runtime at 100% load
- 4 min
- Battery warranty
- 3 yr
- Weighted efficiency
- 91.5%
- Efficiency at 25 / 50 / 75 / 100% load
- 89.8% / 91.7% / 91.6% / 91.2%
- Input power at no load
- 46.9 W
- Rack mountable
- Yes, 2U
- Rated input voltage
- 100-125 V
- Rated output voltage
- 100-125 V
- Connections
- Serial Port,USB Port,Ethernet
- Size (H x W x D)
- 88 x 433 x 600 mm
- Maker take-back program
- Yes
- On the market since
- Jul 2013
- ENERGY STAR certified
- 19 Sep 2018
Source: ENERGY STAR certified uninterruptible power supplies dataset, US EPA, record 2326406, data build 2026-09-29. Figures are as the maker certified them. How we use this data.
Other makers
Machines comparable to the OL3000RTXL2UNTAA
Certified UPS units from other makers within 25% of its VA rating.
| Model | Capacity | Topology | Efficiency | Runtime @ 50% |
|---|---|---|---|---|
| Delta RT-3K | 3,000 VA / 2,700 W | Double Conversion | 92.0% | 12 min |
| Liebert GXT5-3000LVRT2UXL | 3,000 VA / 2,700 W | Multi-Mode Double Conversion | 92.2% | 9 min |
| Vertiv GXT5-3000LVRT2UXL | 3,000 VA / 2,700 W | Multi-Mode Double Conversion | 92.2% | 9 min |
| Eaton 9PX3000GRT | 3,000 VA / 3,000 W | Double Conversion | 92.8% | 11 min |
| Eaton 9PX3000GLRT | 3,000 VA / 3,000 W | Double Conversion | 92.8% | 11 min |
| Eaton 9PX3K3U | 3,000 VA / 3,000 W | Double Conversion | 92.1% | 18 min |
CyberPower
More CyberPower UPS battery backups
| Model | Capacity | Topology | Efficiency | Runtime @ 50% |
|---|---|---|---|---|
| AVRG1000LCD | 1,000 VA / 530 W | Line Interactive | 98.6% | 10 min |
| BL1250U2 | 1,200 VA / 800 W | Line Interactive | 98.7% | 11 min |
| BL1450U | 1,200 VA / 800 W | Line Interactive | 98.7% | 11 min |
| BRG1000AVRLCD | 1,000 VA / 600 W | Line Interactive | 98.5% | 9 min |
| BRG1500AVRLCD | 1,500 VA / 900 W | Line Interactive | 98.6% | 12 min |
| BRG1500AVRLCD2 | 1,500 VA / 900 W | Line Interactive | 98.8% | 11 min |
| CP1000PFCLCD | 1,000 VA / 600 W | Line Interactive | 98.8% | 9 min |
| CP1000PFCLCDa | 1,000 VA / 600 W | Line Interactive | 99.3% | 8 min |