CyberPower UPS, ENERGY STAR certified
CyberPower OL1KRTHD
750 VA / 600 W double conversion UPS.
Capacity
750 VA
600 W real power
Topology
Double Conversion
Efficiency
91.4%
weighted, as tested
Runtime @ 50%
12 min
3 min at full load
A UPS has two ratings and the lower one is the limit. This unit is rated 750 VA and 600 W, so the equipment plugged into its battery outlets should draw no more than about 480 W if you want the usual 20% headroom. How to size a UPS.
Its weighted efficiency of 91.4% compares with a median of 98.7% across 105 certified units within 25% of its capacity. With nothing plugged in it still draws 21.6 W, about $25 a year at 13¢/kWh just to stand ready.
- Maker
- CyberPower
- Model
- OL1KRTHD
- Apparent power rating
- 750 VA
- Real power rating
- 600 W
- Power factor
- 0.80
- Topology
- Double Conversion
- Intended use
- Consumer, Commercial, Data Center
- Battery
- Valve Regulated Lead-acid Battery
- Runtime at 50% load
- 12 min
- Runtime at 100% load
- 3 min
- Battery warranty
- 3 yr
- Weighted efficiency
- 91.4%
- Efficiency at 25 / 50 / 75 / 100% load
- 84.4% / 90.0% / 91.7% / 92.2%
- Input power at no load
- 21.6 W
- Outlets
- 8 (8 battery + surge, 0 surge only)
- Rack mountable
- Yes, 2U
- Rated input voltage
- 100-125 V
- Rated output voltage
- 100-125 V
- Connections
- Serial Port,Ethernet,USB Port
- Size (H x W x D)
- 86 x 433 x 290 mm
- Maker take-back program
- Yes
- On the market since
- Feb 2025
- ENERGY STAR certified
- 3 Jan 2025
Certified under the same record
The maker lists these as the same machine or a variant of it: OL1KRM, OL1KRTHDN, OL1KRMN, OL1KRTHDTAA, OL1KRTHDTAAN, OL1KRTHDLI, OL1KRTHDLIN.
Source: ENERGY STAR certified uninterruptible power supplies dataset, US EPA, record 3892592, data build 2026-09-29. Figures are as the maker certified them. How we use this data.
Other makers
Machines comparable to the OL1KRTHD
Certified UPS units from other makers within 25% of its VA rating.
| Model | Capacity | Topology | Efficiency | Runtime @ 50% |
|---|---|---|---|---|
| Tripp Lite AG-0314 | 750 VA / 450 W | Passive Standby | 99.4% | 9 min |
| Tripp Lite AG-0315 | 750 VA / 450 W | Passive Standby | 98.9% | 9 min |
| APC SMT750C | 750 VA / 500 W | Line Interactive | 98.7% | 15 min |
| APC SMT750RM2UC | 750 VA / 500 W | Line Interactive | 98.7% | 16 min |
| APC SMX750C | 750 VA / 675 W | Line Interactive | 98.7% | 30 min |
| APC SMX750CNC | 750 VA / 675 W | Line Interactive | 98.7% | 30 min |
CyberPower
More CyberPower UPS battery backups
| Model | Capacity | Topology | Efficiency | Runtime @ 50% |
|---|---|---|---|---|
| AVRG1000LCD | 1,000 VA / 530 W | Line Interactive | 98.6% | 10 min |
| BL1250U2 | 1,200 VA / 800 W | Line Interactive | 98.7% | 11 min |
| BL1450U | 1,200 VA / 800 W | Line Interactive | 98.7% | 11 min |
| BRG1000AVRLCD | 1,000 VA / 600 W | Line Interactive | 98.5% | 9 min |
| BRG1500AVRLCD | 1,500 VA / 900 W | Line Interactive | 98.6% | 12 min |
| BRG1500AVRLCD2 | 1,500 VA / 900 W | Line Interactive | 98.8% | 11 min |
| CP1000PFCLCD | 1,000 VA / 600 W | Line Interactive | 98.8% | 9 min |
| CP1000PFCLCDa | 1,000 VA / 600 W | Line Interactive | 99.3% | 8 min |