Skip to content

Vertiv UPS, ENERGY STAR certified

Vertiv eXM 0200kTK16FN01000

200 kVA / 200 kW multi-mode double conversion UPS.

Capacity

200 kVA

200 kW real power

Topology

Multi-Mode Double Conversion

Efficiency

96.1%

weighted, as tested

Runtime @ 50%

10 min

5 min at full load

A UPS has two ratings and the lower one is the limit. This unit is rated 200 kVA and 200 kW, so the equipment plugged into its battery outlets should draw no more than about 160 kW if you want the usual 20% headroom. How to size a UPS.

Its weighted efficiency of 96.1% compares with a median of 96.9% across 27 certified units within 25% of its capacity. With nothing plugged in it still draws 1,253.2 W, about $1,427 a year at 13¢/kWh just to stand ready.

Maker
Vertiv
Model
eXM 0200kTK16FN01000
Apparent power rating
200 kVA
Real power rating
200 kW
Power factor
1.00
Topology
Multi-Mode Double Conversion
Intended use
Consumer, Commercial, Data Center
Battery
Flywheel
Runtime at 50% load
10 min
Runtime at 100% load
5 min
Battery warranty
3 yr
Weighted efficiency
96.1%
Efficiency at 25 / 50 / 75 / 100% load
95.8% / 96.4% / 96.1% / 95.7%
Input power at no load
1,253.2 W
Rack mountable
No
Rated input voltage
228-478 V
Rated output voltage
380-415 V
Connections
Serial Port,Other,USB Port,Ethernet
Size (H x W x D)
2000 x 600 x 1000 mm
Maker take-back program
No
On the market since
Nov 2015
ENERGY STAR certified
23 Jan 2019

Source: ENERGY STAR certified uninterruptible power supplies dataset, US EPA, record 2336442, data build 2026-09-29. Figures are as the maker certified them. How we use this data.

Other makers

Machines comparable to the eXM 0200kTK16FN01000

Certified UPS units from other makers within 25% of its VA rating.

ModelCapacityTopologyEfficiencyRuntime @ 50%
Liebert 51SA200LAA200 kVA / 200 kWMulti-Mode Double Conversion96.5%10 min
Liebert eXM 0200kTK16FN01000200 kVA / 200 kWMulti-Mode Double Conversion96.1%10 min
Schneider Electric GVL400K500DS200 kVA / 200 kWMulti-Mode Double Conversion96.9%-
Schneider Electric GVL200K500DS200 kVA / 200 kWMulti-Mode Double Conversion96.9%-
Schneider Electric GVL300K500DS200 kVA / 200 kWMulti-Mode Double Conversion96.9%-
Schneider Electric Galaxy VL UPS 500 kW 400/480V Start-up 5x8200 kVA / 200 kWMulti-Mode Double Conversion96.9%-

Vertiv

More Vertiv UPS battery backups

ModelCapacityTopologyEfficiencyRuntime @ 50%
10B14763GG103450 kVA / 405 kWMulti-Mode Double Conversion97.2%30 min
10B14789GF103825 kVA / 743 kWMulti-Mode Double Conversion97.7%30 min
47SA040A[0|1|2|3][C|Y][0|F|H|M|G|L][0|1]10 kVA / 10 kWMulti-Mode Double Conversion94.2%34 min
47SA100A[0|1|2|3][C|Y][0|F|H|M|G|L][0|1]60 kVA / 60 kWMulti-Mode Double Conversion95.8%10 min
47SA120A[0|1|2|3][C|Y][0|F|H|M|G|L][0|1]120 kVA / 120 kWMulti-Mode Double Conversion95.6%10 min
51SA030QAA30 kVA / 30 kWMulti-Mode Double Conversion96.3%10 min
51SA030QBA30 kVA / 30 kWMulti-Mode Double Conversion95.2%10 min
51SA050BAA50 kVA / 50 kWMulti-Mode Double Conversion96.4%10 min

All Vertiv UPS battery backups