Vertiv UPS, ENERGY STAR certified
Vertiv eXM 0200kTK16FN01000
200 kVA / 200 kW multi-mode double conversion UPS.
Capacity
200 kVA
200 kW real power
Topology
Multi-Mode Double Conversion
Efficiency
96.1%
weighted, as tested
Runtime @ 50%
10 min
5 min at full load
A UPS has two ratings and the lower one is the limit. This unit is rated 200 kVA and 200 kW, so the equipment plugged into its battery outlets should draw no more than about 160 kW if you want the usual 20% headroom. How to size a UPS.
Its weighted efficiency of 96.1% compares with a median of 96.9% across 27 certified units within 25% of its capacity. With nothing plugged in it still draws 1,253.2 W, about $1,427 a year at 13¢/kWh just to stand ready.
- Maker
- Vertiv
- Model
- eXM 0200kTK16FN01000
- Apparent power rating
- 200 kVA
- Real power rating
- 200 kW
- Power factor
- 1.00
- Topology
- Multi-Mode Double Conversion
- Intended use
- Consumer, Commercial, Data Center
- Battery
- Flywheel
- Runtime at 50% load
- 10 min
- Runtime at 100% load
- 5 min
- Battery warranty
- 3 yr
- Weighted efficiency
- 96.1%
- Efficiency at 25 / 50 / 75 / 100% load
- 95.8% / 96.4% / 96.1% / 95.7%
- Input power at no load
- 1,253.2 W
- Rack mountable
- No
- Rated input voltage
- 228-478 V
- Rated output voltage
- 380-415 V
- Connections
- Serial Port,Other,USB Port,Ethernet
- Size (H x W x D)
- 2000 x 600 x 1000 mm
- Maker take-back program
- No
- On the market since
- Nov 2015
- ENERGY STAR certified
- 23 Jan 2019
Source: ENERGY STAR certified uninterruptible power supplies dataset, US EPA, record 2336442, data build 2026-09-29. Figures are as the maker certified them. How we use this data.
Other makers
Machines comparable to the eXM 0200kTK16FN01000
Certified UPS units from other makers within 25% of its VA rating.
| Model | Capacity | Topology | Efficiency | Runtime @ 50% |
|---|---|---|---|---|
| Liebert 51SA200LAA | 200 kVA / 200 kW | Multi-Mode Double Conversion | 96.5% | 10 min |
| Liebert eXM 0200kTK16FN01000 | 200 kVA / 200 kW | Multi-Mode Double Conversion | 96.1% | 10 min |
| Schneider Electric GVL400K500DS | 200 kVA / 200 kW | Multi-Mode Double Conversion | 96.9% | - |
| Schneider Electric GVL200K500DS | 200 kVA / 200 kW | Multi-Mode Double Conversion | 96.9% | - |
| Schneider Electric GVL300K500DS | 200 kVA / 200 kW | Multi-Mode Double Conversion | 96.9% | - |
| Schneider Electric Galaxy VL UPS 500 kW 400/480V Start-up 5x8 | 200 kVA / 200 kW | Multi-Mode Double Conversion | 96.9% | - |
Vertiv
More Vertiv UPS battery backups
| Model | Capacity | Topology | Efficiency | Runtime @ 50% |
|---|---|---|---|---|
| 10B14763GG103 | 450 kVA / 405 kW | Multi-Mode Double Conversion | 97.2% | 30 min |
| 10B14789GF103 | 825 kVA / 743 kW | Multi-Mode Double Conversion | 97.7% | 30 min |
| 47SA040A[0|1|2|3][C|Y][0|F|H|M|G|L][0|1] | 10 kVA / 10 kW | Multi-Mode Double Conversion | 94.2% | 34 min |
| 47SA100A[0|1|2|3][C|Y][0|F|H|M|G|L][0|1] | 60 kVA / 60 kW | Multi-Mode Double Conversion | 95.8% | 10 min |
| 47SA120A[0|1|2|3][C|Y][0|F|H|M|G|L][0|1] | 120 kVA / 120 kW | Multi-Mode Double Conversion | 95.6% | 10 min |
| 51SA030QAA | 30 kVA / 30 kW | Multi-Mode Double Conversion | 96.3% | 10 min |
| 51SA030QBA | 30 kVA / 30 kW | Multi-Mode Double Conversion | 95.2% | 10 min |
| 51SA050BAA | 50 kVA / 50 kW | Multi-Mode Double Conversion | 96.4% | 10 min |