Skip to content

V7 UPS, ENERGY STAR certified

V7 UPS2URM3000DC-NC-1N

3,000 VA / 2,740 W multi-mode double conversion UPS.

Capacity

3,000 VA

2,740 W real power

Topology

Multi-Mode Double Conversion

Efficiency

91.6%

weighted, as tested

Runtime @ 50%

10 min

3 min at full load

A UPS has two ratings and the lower one is the limit. This unit is rated 3,000 VA and 2,740 W, so the equipment plugged into its battery outlets should draw no more than about 2,192 W if you want the usual 20% headroom. How to size a UPS.

Its weighted efficiency of 91.6% compares with a median of 93.1% across 95 certified units within 25% of its capacity. With nothing plugged in it still draws 54.9 W, about $63 a year at 13¢/kWh just to stand ready.

Maker
V7
Model
UPS2URM3000DC-NC-1N
Apparent power rating
3,000 VA
Real power rating
2,740 W
Power factor
0.91
Topology
Multi-Mode Double Conversion
Intended use
Consumer, Commercial, Data Center
Battery
Valve Regulated Lead-acid Battery
Runtime at 50% load
10 min
Runtime at 100% load
3 min
Battery warranty
1 yr
Weighted efficiency
91.6%
Efficiency at 25 / 50 / 75 / 100% load
89.3% / 91.7% / 91.8% / 91.3%
Input power at no load
54.9 W
Rack mountable
Yes, 2U
Rated input voltage
100-125 V
Rated output voltage
100-125 V
Connections
Ethernet,Serial Port,USB Port
Size (H x W x D)
88 x 438 x 630 mm
Maker take-back program
No
On the market since
Jun 2026
ENERGY STAR certified
14 Jul 2022

Source: ENERGY STAR certified uninterruptible power supplies dataset, US EPA, record 2398571, data build 2026-09-29. Figures are as the maker certified them. How we use this data.

Other makers

Machines comparable to the UPS2URM3000DC-NC-1N

Certified UPS units from other makers within 25% of its VA rating.

ModelCapacityTopologyEfficiencyRuntime @ 50%
CyberPower PR3000RTXL2UHVA3,000 VA / 3,000 WLine Interactive98.9%11 min
Delta RT-3K3,000 VA / 2,700 WDouble Conversion92.0%12 min
CyberPower OL3000RTXL2UHV3,000 VA / 2,700 WDouble Conversion92.0%11 min
CyberPower OL3000RTXL2UHVN3,000 VA / 2,700 WDouble Conversion92.0%11 min
CyberPower OL3000RTXL2UHVTAA3,000 VA / 2,700 WDouble Conversion92.0%11 min
CyberPower OL3000RT JP3,000 VA / 2,700 WDouble Conversion91.5%11 min

V7

More V7 UPS battery backups

ModelCapacityTopologyEfficiencyRuntime @ 50%
UPS1RM2U3000-1N3,000 VA / 2,700 WLine Interactive98.5%12 min
UPS2URM1500DC-NC-1N1,500 VA / 1,430 WMulti-Mode Double Conversion91.4%10 min

All V7 UPS battery backups