UPSONIC UPS, ENERGY STAR certified
UPSONIC UTX+ 20KVA Power Module
20 kVA / 20 kW double conversion UPS, model number UPS UPSONIC UTX+ 208VAC.
Capacity
20 kVA
20 kW real power
Topology
Double Conversion
Efficiency
94.4%
weighted, as tested
Runtime @ 50%
-
not reported by the maker
A UPS has two ratings and the lower one is the limit. This unit is rated 20 kVA and 20 kW, so the equipment plugged into its battery outlets should draw no more than about 16 kW if you want the usual 20% headroom. How to size a UPS.
Its weighted efficiency of 94.4% compares with a median of 95.6% across 45 certified units within 25% of its capacity. With nothing plugged in it still draws 242.0 W, about $276 a year at 13¢/kWh just to stand ready.
- Maker
- UPSONIC
- Model
- UTX+ 20KVA Power Module
- Model number
- UPS UPSONIC UTX+ 208VAC
- Apparent power rating
- 20 kVA
- Real power rating
- 20 kW
- Power factor
- 1.00
- Topology
- Double Conversion
- Intended use
- Commercial, Data Center
- Weighted efficiency
- 94.4%
- Efficiency at 25 / 50 / 75 / 100% load
- 92.4% / 94.0% / 93.6% / 93.0%
- Input power at no load
- 242.0 W
- Rack mountable
- Yes, 1U
- Modular
- Yes
- Rated input voltage
- 120-208 V
- Rated output voltage
- 120-208 V
- Connections
- None
- Size (H x W x D)
- 130 x 490 x 737 mm
- Maker take-back program
- No
- On the market since
- Jan 2020
- ENERGY STAR certified
- 11 Jan 2023
Source: ENERGY STAR certified uninterruptible power supplies dataset, US EPA, record 2407035, data build 2026-09-29. Figures are as the maker certified them. How we use this data.
Other makers
Machines comparable to the UTX+ 20KVA Power Module
Certified UPS units from other makers within 25% of its VA rating.
| Model | Capacity | Topology | Efficiency | Runtime @ 50% |
|---|---|---|---|---|
| Schneider Electric Galaxy VS 30kW 480V w/o Batteries, Start-up 5x8 | 20 kVA / 20 kW | Multi-Mode Double Conversion | 95.9% | - |
| Schneider Electric GVSUPS80KGS | 20 kVA / 20 kW | Multi-Mode Double Conversion | 95.9% | - |
| Schneider Electric Galaxy VS 40kW 480V w/o Batteries, Start-up 5x8 | 20 kVA / 20 kW | Multi-Mode Double Conversion | 95.9% | - |
| Schneider Electric Galaxy VS 20kW 480V w/o Batteries, Start-up 5x8 | 20 kVA / 20 kW | Multi-Mode Double Conversion | 95.9% | - |
| Schneider Electric Galaxy VS 50kW 480V w/o Batteries, Start-up 5x8 | 20 kVA / 20 kW | Multi-Mode Double Conversion | 95.9% | - |
| Schneider Electric Galaxy VS 100kW 480V w/o Batteries, Start-up 5x8 | 20 kVA / 20 kW | Multi-Mode Double Conversion | 95.9% | - |