Ablerex UPS, ENERGY STAR certified
Ablerex MP410K0DCALA
10 kVA / 10 kW other UPS.
Capacity
10 kVA
10 kW real power
Topology
Other
Efficiency
94.2%
weighted, as tested
Runtime @ 50%
-
not reported by the maker
A UPS has two ratings and the lower one is the limit. This unit is rated 10 kVA and 10 kW, so the equipment plugged into its battery outlets should draw no more than about 8,000 W if you want the usual 20% headroom. How to size a UPS.
Its weighted efficiency of 94.2% compares with a median of 95.1% across 62 certified units within 25% of its capacity. With nothing plugged in it still draws 83.5 W, about $95 a year at 13¢/kWh just to stand ready.
- Maker
- Ablerex
- Model
- MP410K0DCALA
- Apparent power rating
- 10 kVA
- Real power rating
- 10 kW
- Power factor
- 1.00
- Topology
- Other
- Intended use
- Commercial
- Weighted efficiency
- 94.2%
- Efficiency at 25 / 50 / 75 / 100% load
- 94.0% / 94.8% / 94.4% / 93.5%
- Input power at no load
- 83.5 W
- Rack mountable
- No
- Rated input voltage
- 200-240 V
- Rated output voltage
- 200-240 V
- Connections
- Serial Port,USB Port
- Size (H x W x D)
- 88 x 440 x 700 mm
- Maker take-back program
- Yes
- On the market since
- Jan 2026
- ENERGY STAR certified
- 13 Jan 2026
Source: ENERGY STAR certified uninterruptible power supplies dataset, US EPA, record 4572724, data build 2026-09-29. Figures are as the maker certified them. How we use this data.
Other makers
Machines comparable to the MP410K0DCALA
Certified UPS units from other makers within 25% of its VA rating.
| Model | Capacity | Topology | Efficiency | Runtime @ 50% |
|---|---|---|---|---|
| Delta RT-10K | 10 kVA / 10 kW | Double Conversion | 95.2% | 12 min |
| Liebert GXT5-10KIRT5UXLN | 10 kVA / 10 kW | Multi-Mode Double Conversion | 95.1% | 7 min |
| Vertiv GXT5-10KIRT5UXLN | 10 kVA / 10 kW | Multi-Mode Double Conversion | 95.1% | 7 min |
| Liebert GXE-10k00TLA102C00 | 10 kVA / 9,000 W | Multi-Mode Double Conversion | 95.5% | 19 min |
| Vertiv GXE-10k00TLA102C00 | 10 kVA / 9,000 W | Multi-Mode Double Conversion | 95.5% | 19 min |
| Liebert GXT5-10KMVRT6UXLN | 10 kVA / 10 kW | Multi-Mode Double Conversion | 93.9% | 9 min |
Ablerex
More Ablerex UPS battery backups
| Model | Capacity | Topology | Efficiency | Runtime @ 50% |
|---|---|---|---|---|
| AP21000BCALA | 1,000 VA / 1,000 W | Other | 90.5% | 11 min |
| AP21000BTALA | 1,000 VA / 1,000 W | Other | 90.6% | 11 min |
| AP21000DCALB | 1,000 VA / 1,000 W | Other | 90.7% | 11 min |
| AP21500BCALA | 1,500 VA / 1,380 W | Other | 90.4% | 11 min |
| AP21500BTALA | 1,500 VA / 1,380 W | Other | 90.6% | 11 min |
| AP22000BCALA | 2,000 VA / 1,840 W | Other | 91.6% | 11 min |
| AP22000BTALA | 2,000 VA / 1,840 W | Other | 91.9% | 11 min |
| AP22000DCALB | 2,000 VA / 2,000 W | Other | 91.4% | 11 min |